Lack of reliable specifications of loudspeakers and loudspeaker cables, as well as complex nature
of combined total impedance of a loudspeaker line makes it impossible to predict or calculate
impedance at 20kHz without real measurements.
In order to effectively assess loudspeaker lines monitoring in 4EVAC systems, it is necessary to use
Live Monitoring
feature of the 4EVAC Manager GUI application, where you can observe exact
impedance at 20kHz of each loudspeaker line, in real time. (More information on how to use 4EVAC
Manager you can find in 4EVAC Manager User Manual).
Live Monitoring in 4EVAC Manager GUI
In the screenshot above you can see Live monitoring window of 4E-SW6. For each output line
following parameters are displayed in real time:
•
Impedance
This is the actual 20kHz impedance measured in real time by the system. Values below 10Ω
are considered as short circuit. Values above 5kΩ are considered as open line.
•
Reference impedance
This is the reference impedance saved in system memory during impedance calibration.
•
Deviation
This is the difference between reference impedance and actually measured impedance,
expressed in %. Deviation relates directly to Tolerance setting of EOL monitoring (see
4EVAC Manager User Manual)