4E-CMT installation and user guide 

Author: 

DD 

 

 

 

Page 7 of 13 

  

 

4.1.3.

 

Network cabling 

4EVAC network features a full duplex RS-422 data link and 24V DC power to remote devices. 
If you’re building a distributed system using the 4EVAC network, you should make physical links between 

devices using the right cables. Cabling should meet the following requirements: 

1.

 

Crossover twisted-pair cable (compatible with Ethernet crossover) 

 

 

 

2.

 

CAT5e or higher for maximum distance of 250m. 

3.

 

Non-CAT / lower than CAT5e: 250m not guaranteed. 

4.

 

Shield required (at least FTP) 

 
NOTE: If you use a straight cable, the device will power up but the Tx/Rx data terminals will not be properly 

connected. This will result in a communication fault between the L-Net device and the main controller unit. 

The L-Net device will not be able to initialize, thus will remain in boot-sequence, not operational. 
 
Caution! Use only crossover cables and keep correct the pinout! Connecting power pins to data pins will 

damage the network port.

 

 
 

 

pin number

pin number

GND

shield

shield

GND

RX+

1

1

RX+

RX-

2

2

RX-

TX+

3

3

TX+

power +

4

4

power +

power -

5

5

power -

TX-

6

6

TX-

power +

7

7

power +

power -

8

8

power -

pin number

pin number

GND

shield

shield

GND

RX+

1

1

RX+

RX-

2

2

RX-

TX+

3

3

TX+

power +

4

4

power +

power -

5

5

power -

TX-

6

6

TX-

power +

7

7

power +

power -

8

8

power -

xover type A cable

xover type B cable

Summary of Contents for 4E-CMT

Page 1: ...t explains how the 4E CMT should be installed and configured The installation instructions are addressed to trained technical personnel such as installers service technicians and commissioning enginee...

Page 2: ...do I start 3 3 Configuration settings 4 4 Hardware installation and settings 5 L Net 5 4 1 1 Network ports 5 4 1 2 Redundant link 6 4 1 3 Network cabling 7 Device ID 8 5 Front Panel 9 PAGING tab 9 5 1...

Page 3: ...tures are available as well as user defined non emergency events 4E CMT does not support microphone surveillance and does not offer any emergency functions and is therefore not suitable as an EN54 com...

Page 4: ...or hardware damage causing serious system malfunction and therefore are strictly prohibited and void manufacturer s warranty 3 Configuration settings Settings for the 4E CMT are included in the confi...

Page 5: ...ations per L Net port A maximum of 16 stations per single 4EVAC main unit total sum of all 3 L net ports The microphone station may also be daisy chained together with other L Net devices Compact 500...

Page 6: ...ther L Net devices NOTE The device is equipped with a power link jumper which by default is in the ON position pass through power over L Net In order to a create redundant link the jumper must be move...

Page 7: ...d at least FTP NOTE If you use a straight cable the device will power up but the Tx Rx data terminals will not be properly connected This will result in a communication fault between the L Net device...

Page 8: ...set the Device ID you must access the rotary switches on the back side of the unit 1 Remove the steel plate covering back of the console 2 Identify high significant and low significant rotary switche...

Page 9: ...ection In order to start paging message first select a zone or group of zones on the left section of the screen If there are more than 6 zones accessible use the scroll arrow button to scroll through...

Page 10: ...ging in all zones available on this panel ALL CALL 5 1 4 Stop message BGM Select zones where a message BGM audio signal is being transmitted and press STOP This will reset these zones stopping all aud...

Page 11: ...of zones For more information about programming events please look in the user manual of the 4EVAC Manager where all configuration settings are explained LOG tab Under the LOG tab you will find the sy...

Page 12: ...gital audio format 24 kHz sampling ADPCM compressed Audio processing Fixed BP filter fixed dynamics compression Local network interface Architecture Master slave up to 16 slave devices per C500 main u...

Page 13: ...651BC Berkel Rodenrijs 4E CMT installation and user guide Author DD Page 13 of 13 M A D E I N T H E N E T H E R L A N D S 4EVAC is a trade name of Hacousto Holland bv Industrieweg 87 2651BC Berkel Rod...

Reviews: