3. The required cable specification, quantity, direction and 
laying position need to match construction requirements, 

and cable length depends on actual position;

 

4. All the cable cannot have break-down and terminal in the 

middle;

 

5. Cables should be straight in the hallways and turning;

 

6. Cable should be straight in the groove, and cannot beyond 
the groove in case of holding back the inlet and outlet holes. 
Cables should be banded and fixed when they are out of the 

groove;

 

7. User cable should be separated from the power lines. 
Cables, power lines and grounding lines cannot be 
overlapped and mixed when they are in the same groove 
road. When cable is too long, it cannot hold down other 

cable, but structure in the middle of alignment rack;

 

8. Pigtail cannot be tied and swerved as less as possible. 
Swerving radius cannot be too small (small swerving causes 
terrible loss of link). Its banding should be moderate, not too 

tight, and should be separated from other cables;

 

9. It should have corresponding simple signal at both sides 
of the cable for maintaining. 

Specification

 

Ethernet port 

Standard: 10Base-T, 100Base-TX 
Protocol: Support Modbus TCP, Modbus RTU, Modbus ASCII, IP, 

APR, ICMP, DNS and DHCP 

Signal: Rx+, Rx-, Tx+, Tx- 
Speed: 10/100Mbps 
Working: Full-duplex and half duplex 
Transfer distance: 100m 
Connector: RJ45 

Serial port 

Serial port number: 2 ports RS-232 or 2 ports RS-485/422 

RS-232 signal: DCD, RXD, TXD, DTR, GND, DSR, RTS, CTS 
RS-485 signal: D+(A), GND, D-(B) 
RS-422 signal: T+, T-, GND, R+, R- 
Parity bit: None, Even, Odd, Space, Mark 
Data bit: 7bit, 8bit 
Stop bit: 1bit, 2bit 
Baud rate: 300bps

115200bps 

RS-232 Transfer distance: no more than 15m 
RS-232 connector: RJ45 
RS-485/422 transfer distance: 1200m 
RS-485/422 connector: 5 bits terminal block 
Protection: class 3 static 
Work mode: RTU Slave, RTU Master, ASCII Slave,   

and ASCII Master 

Multiple master and multi slave connection: 
Master mode: maximum 32 TCP slave   
Slave mode: 16 TCP master (each master allows 32 commands) 

LED Indicator 

Power (PWR) 
Ethernet port connect statue (Link) 
Serial port data indicator: TX1~TX2, RX1~RX2

;

 

Power requirements 

Input voltage: 9~48VDC 
Type of input: 2 bits terminal block 

Consumption 

 

GW1102-2D(RS-232)-P(9~48VDC) 

No-load consumption: 0.79W@9V 
Full-load consumption: 0.86W@9V 

 

GW1102-2D(RS-485)-P(9~48VDC) 

No-load consumption: 0.90W@9V 
Full-load consumption: 1.25W@9V 

Mechanical 

Shell: IP40 protection, metal shell 

Installation: Wall mounting 
Weight: 250g 
Size (L×W×H): 100mm×69mm×22mm 

Environment limits 

Working temperature: -40~75

 

Storage temperature: -40~85

 

Relative humidity: 5%~95%

non-condensing

 

Standard 

EMI: EN 55022 Class A, FCC Part 15 Subpart B Class A 
EMS: EN 61000-4-2 (ESD), Level 3 
Shock: IEC 60068-2-27 
Free fall: IEC 60068-2-32 
Vibration: IEC 60068-2-6   

Warranty 

Warranty time: 3 years 

Certificates 

CE, FCC, RoHS, UL508 (pending) 