- 3 - 

When the CAN232 converter is used as the CAN-bus network 

terminal, the two pin is connected to a resistance of 120

Ω, 

otherwise no need to install a 120

Ω resistor. 

Serial port connection 

RS-232 side is DB9 Female. The 3-PIN definition is as follows: 

PIN 

RS-232 

— 

— 

TxD 

Transmit data 

RxD 

Received data 

— 

— 

GND 

Signal ground 

6/7/8/9 

— 

— 

LED Indicator

 

LED indictor light on the top  panel of product, the function of 

each LED is described in the table as below. 

System statue LED 

LED 

Indicate 

Description 

PWR 

ON 

Power is connected/Function natural

 

OFF 

Power is disconnected or function 

nu-natural

 

CAN 

ON 

CAN-Bus port connect successfully 

Flashing 

CAN-Bus port has data transmission 

OFF 

CAN-Bus port connect unsuccessfully 

RS-232 

ON 

Serial port connect successfully 

Flashing 

In transmitting/ receiving data 

OFF 

None data receive/ transmit 

Installation

 

Before installation, confirm that the work environment meet the 

installation require, including the power needs and abundant 

space. Whether it is close to the connection equipment and other 

equipments are prepared or not.   

1. Avoid in the sunshine, keep away from the heat fountainhead or 

the area where in intense EMI. 

2. Examine the cables and plugs that installation requirements.   

3. Power: 9 ~ 48VDC 

4. Environment: working temperature: -40

75

 

Storage Temperature: -40

85

 

Relative humidity 5%

95% 

5. Support wall or DIN-Rail mounted

 

Wiring Requirements 

Cable laying need to meet the following requirements,

 

1.

 

It is needed to check whether the type, quantity and 

specification of cable match the requirement before cable 

laying; 

2.

 

It is needed to check the cable is damaged or not, factory 

records and quality assurance booklet before cable laying; 

3.

 

The required cable specification, quantity, direction and 

laying position need to match construction requirements, and 

cable length depends on actual position; 

4.

 

Cables should be straight in the hallways and turning; 

5.

 

Cable should be straight in the groove, and cannot beyond the 

groove in case of holding back the inlet and outlet holes. 

Cables should be banded and fixed when they are out of the 

groove; 

6.

 

User cable should be separated from the power lines. Cables, 

power lines and grounding lines cannot be overlapped and 

mixed when they are in the same groove road. When cable is 

too long, it cannot hold down other cable, but structure in the 

middle of alignment rack; 

7.

 

It should have corresponding simple signal at both sides of the 

cable for maintaining. 

Specification

 

Serial Interface 

Standard: RS-232 

RS-232 signal: RXD, TXD, GND 

Parity bit: None, Even, Odd, Space, Mark 

Data bit: 8bit 

Stop bit: 1bit, 2bit 

Band rate: 300bps

115200bps 

Loading: point to point 

Transfer distance: no more than 15m 

Connector: DB9 Female 

CAN-Bus Interface 

Standard: CAN2.0A, CAN2.0B 

CAN-Bus signal: CANL, CANH, GND, RES+, RES- 

Band rate: 2.5K

1Mbps 

Transfer distance: 40m~10Km 

Power supply 

Input voltage: 9~48VDC 

Type of input: 2 bits terminal block 

No-load consumption: .0.86W@9VDC 

Full-load consumption: 0.89W@9VDC 

Power support reverse connection 

Working environment 

Working temperature: -40

75

 

Storage temperature: -40

85

 

Relative Humidity: 5%~95% (no condensation) 

Mechanical Structure 

Shell: IP40 protect grade, metal shell 

Installation: DIN-Rail or Wall mounting 

Weight: 238g 

Size (W×H×D): 69mm×22mm×100mm 

Industry Standard 

EMI: FCC Part 15, CISPR (EN55022) class A   

EMS: EN61000-4-2 (ESD), Level 3 

Shock: IEC 60068-2-27 

Free fall: IEC 60068-2-32 

Vibration: IEC 60068-2-6   

Certification 

CE, FCC, RoHS, UL508 (Pending) 

Warranty: 

3 years 

DB9 Female 