background image

- 4 - 

Power supply 

External power supply: DC5V 

Built-in power supply: 24VDC, 48VDC or 220VAC optional. 

Load consumption: 4W 

Working environment 

Working temperature: -10

60

 

Storage temperature: -20

70

 

Relative Humidity: 5%~95% (no condensation) 

Mechanical Structure 

Shell: Metal shell 

Installation: DIN-Rail mounting 

Size (L×W×H):

 

94mm×71mm×26mm (External power supply) 

115mm×173mm×30mm (Built in power supply) 

Certification 

CE, FCC, RoHS 

Warranty: 

3 years 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Applications: 

 

 

Extending 10/100/100M Ethernet data distance   

 

Troubleshooting instructions: 

1.Make sure the power is connected and turned on.   

2.Make sure the converter Ethernet and fiber optic cables are 

connected properly.   

3.Check the connections according to the connection diagram.   

4.Check the LED Indication status and identify possible problems 

from the Indication LED table above.   

 

Note: 

1. Media  Converter is  a sensitive electronic item,  please  do 

handle  with extra care on delivery, shifting and humidity. 

2. This unit will be warranty for 3 years. 

3. Whenever there is a problem regarding the quality issue within 

the warranty period, we will take the responsibility to repair 

with free. 

4. After the warranty period,  we  will  charge accordingly 

depending  on the fault or damage. 

5. Whenever  there  is  a  fault,  you  can  contact our  technical 

support  after you identify the problem and the alarm. 

 

Common Problems: 

1. PWR power supply indicator lamp not lighting 

    Cause: 

1. Power supply not properly connected   

2. Protector tube damaged   

3. Power input tie-line in reverse connection   

4. Internal power supply circuit with failure 

Solution:

 

1

. Check power switch and jack   

2. Replace protector tube   

3. Correct power supply line connection   

4. Returned to the manufacturer for repair. 

2. FX(Fiber Link Port) indicator lamp not lighting 

  Cause: 

Optic fiber port link is fault.

 

Solution: 

1. Check fiber optic is link or not. 

2. Check fiber optic loss is high. 

3. Clean the connector of optic interface. 

4. Insert the well connector in place. 

5. Returned to the manufacturer for repair. 

3. TP-TX(Ethernet Port) indicator lamp not lighting 

Cause: 

Ethernet port link is fault. 

Solution: 

1. Check Ethernet(RJ45) line is link or not. 

2. Check Ethernet(RJ45) port is loose. 

3. Check the rate of selected media converter 

4. Check the rate of Network. 

5. Returned to the manufacturer for repair. 

4. Network packet loss 

Solution: 

1. Check Ethernet rate or full/half duplex is 

matched

 or not.   

2. Ethernet(RJ45) port is loose contact, or optic port is loose 

contact and soiled. 

3. Ethernet cable not comply with Ethernet standard. 