7. CONTROL

7.1. COMMUNICATION PROTOCOL - MODBUS RTU

*Address of module 0x01

Operational parameters of communication line  RS485 MODBUS (RTU):

9600Bd
1 start bit 
8 data bits         
1 bit even parity 
1 stop bit
Each module must support even parity. If parity is not used, it is replaced by second stop bit.

Communication method:

Master – control system (BMS)
Slave – electronics Module D (Modbus module)

Only the control system can be connected.
After the first connection of power supply, the module is in the OFF state. The requested operational mode must be sent by the superior control system! After 
the subsequent disconnection of the power supply, the module remembers its last operational mode.

Communication connector numbers:

A - 6
B - 7
GND - 8

MODBUS RTU:

In the RTU mode, every 8-bit byte of message contains two 4-bit hexadecimal characters. The   transmission of a message must be continuous, the spaces 
between the characters must not be longer than 1.5 character. The beginning and end of the message is identified according to the bus rest longer than 3.5 
character. The RTU frame format is shown in the picture.

General structure of telegram [hex]:

Beginning

Address

Function

Data

CRC

End

> 3.5 characters

8 bits

8 bits

N * 8 bits

16 bits

> 3.5 characters

Data block length

Size of

  ADU on RS-485 = 

253 bytes PDU + address(1 byte) + CRC (2 bytes) =

 256 bytes

Address 

Master has not any specific address, only slave units have to have an address unique in all MODBUS site.

CRC

Field with generating polynom x16 + x15 + x2 + 1.

7.2. TABLE OF KEY CHARACTERS AND CONFIGURATION DATA

Factory Driver: 

Intended for hardware setup  (READ/WRITE)

Address

Name

Info

Min. Value

Max. Value

Default

Factory set register - without valid FactoryPass only read

10001

AC_Switch

0 - AC3

1 - AC5

0

1

0

10002

MaxFlowManual

% of fan power

70

100

100

10003

MinFlowManual

% of fan power

0

40

20

10004

Postheat_1

0 - none

1 - electric

2 - water

0

2

0

10005

MotorEC_set

0 - PWM

1 - analog (0-10V)

0

1

0

10006

TempEXT1

0 - non

1 - used

0

1

0

 
            At the IC-ModBus regulator, it is necessary to always set AC5 on address 10001 (five-degree module)

Summary of Contents for IC-ModBus

Page 1: ...INSTALLATION AND SERVICE MANUAL IC ModBus EN H04 0221 0216 00 1 1 P04 0221 0216 00 ...

Page 2: ...e properly read the whole manual The manufacturer reserves the right to make changes including the technical documentation without prior notice Please save this manual for future use The service manual is a part of the product Conformity declaration The product has been designed manufactured placed on the market complies with all applicable regulations and is in compli ance with the requirements o...

Page 3: ... supplier Never try to put a damaged product into operation If a product is not unpacked immediately after delivery it has to be stored in a dry interior with a maximum tempera ture range from 5 C to 40 C This product should not be used by persons including chil dren whose physical sensory or mental disability or lack of experience and knowledge is insufficient for the safe use of the product if t...

Page 4: ...ss since 1995 5 TECHNICAL SPECIFICATIONS Type Number of phases pcs Voltage V Frequency Hz Max fans current A Weight kg IC M AC5 04 1 230 50 60 4 13 5 IC M AC5 07 1 230 50 60 7 15 IC M AC5 16 1 230 50 60 16 23 4 DIMENSIONS Dimensions for wall mounted regulation ...

Page 5: ...disassembling The regulator is attached using screws and dowels on a wall or bolts There must not be any flammable materials within a distance of 100 mm from the regulator TECHNICAL INFORMATION After installation of the regulator on the wall we recommend se parating the inner part electronics transformer from the regula tion box for easier manipulation 1 2 6 3 ELECTRICAL WIRING AND ELECTRICAL ASSE...

Page 6: ...driver 10005 17 TACHO EC motor IC ModBus is ready for control of AC and EC motors 6 4 DESCRIPTION OF CONNECTORS Description electric heat Description water heat L Power supply phase 230V N Neutral bridge N Grounding bridge PE L Fan Fan control phase output Heat 1 Heating degree 1 electric heat output 230V with Imax 3A Controlling voltage of the actua ting mechanism water heat output 230V Heat 2 He...

Page 7: ...ELECTRIC HEAT 6 6 EXAMPLE OF WIRING OF SHUTTER WITH WATER HEAT L FAN L L L Heat1 Heat2 L1 L2 L3 L FAN L L L Heat1 Heat2 Servodrive water valve Fan motor IC ModBus BMS External con tact Input Temperature sensor Input IC ModBus Fan motor Electric heat 1 level 2 level PE N BMS External contact Input Temperature sensor Input PE N ...

Page 8: ...between the characters must not be longer than 1 5 character The beginning and end of the message is identified according to the bus rest longer than 3 5 character The RTU frame format is shown in the picture General structure of telegram hex Beginning Address Function Data CRC End 3 5 characters 8 bits 8 bits N 8 bits 16 bits 3 5 characters Data block length Size of ADU on RS 485 253 bytes PDU ad...

Page 9: ...ster read only Factory reset no effect 15000 UnitStatus 0 OFF 1 ON 2 COOLDOWN 0 2 15001 Sensor Status 1 TempEXT1_Error 0 TempEXT1_OK 0 1 15002 StatusDI1 1 DI_open 0 DI_closed 0 1 15003 StatusDI2 1 DI_TACHO_pulzy 0 DI TACHO_error 0 1 15004 AirFlowFanManual 0 OFF 1 20 1 speed 21 40 2 speed 41 60 3 speed 61 80 4 speed 81 100 5 speed 0 100 15005 AirFlowFanManualEC 0 OFF 1 100 PWM 0 100 15006 PowerPost...

Page 10: ...e to process it normally it returns a normal answer to the client If a server does not receive a request due to a communication failure it does not return any answer On the side of the client the time limit for answer receipt expires If a server receives a request but detects a communication failure parity CRC it does not return any answer On the side of client the time limit for answer receipt ex...

Page 11: ...intended for use at programming The server is busy with executing a long standing command 08 Memory parity failure Code intended for use at work with files Server discovered a parity failure while trying to read the file Supported telegrams Modbus Modbus Module MODBUS failure coder Code Name Meaning 03 READ HOLDING REGISTER according to Modbus standard 04 READ INPUT REGISTER according to Modbus st...

Page 12: ...ntact our customer service or technical support department Contact 2VV s r o Fáblovka 568 533 52 Pardubice Czech Republic Internet http www 2vv cz Copyright 2VV All rights reserved The producer is not responsible for damages incurred on the device which were caused by an inexpert installation and service which are contrary with the manual and conventions during installation and service of ventilat...

Reviews: