20
2VV.
Creating innovative solutions for you and your business since 1995.
The unit is not designed for air containing flammable or ex-
plosive mixtures, chemical vapours, heavy dust, soot, grease,
toxins, pathogenic organism, etc.
The electric protection index of units is IP 43 (intended for
outdoor environments).
6.1-1 Access distances needed for servicing
the units
Models V/U
a
700
800
1000
800
1500
900
2000
900
3000
1200
4500
1200
5500
1500
7500
1500
9000
1500
12000
1500
6.1 seLect unIt LocAtIon
TECHNICAL DATA
Units intended for outdoor installation may only be installed
in the an unprotected outdoor environment with with tem-
peratures between -20°C to +60°C
For outdoor installations it is necessary to use rain protected
roofs. Outdoor installation is possible on side connection
units only.
Rein-protected roofs
ALFA 85 V
code
700
ROOF-HR85-070
1000
ROOF-HR85-100
1500/2000
ROOF-HR85-150-200
3000/4500
ROOF-HR85-300-450
5500/7000
ROOF-HR85-550-750
9000/12000
ROOF-HR85-900-12K
•
The unit should use air flow with temperatures between
-20°C to +60°C and relative humidity up to 90 %.
6. INSTALLATION
60