EA

SY

ELECTRIC LOCK CONNECTION

SPECIFICATION

1) Door Lock Controlled with Internal Power

1. The door lock is limited to 12Vdc, and holding current must be less 
than 250mA when using internal power supply mode.

2. The Unlock Mode Parameter must be set to 0 (by default).

3.  Jumper  set  to  1-2  position  for  power-off-to-unlock  safety 
type(

Normally  closed  mode

);  set  to  2-3  position  for  power-on-to 

-unlock type(

Normally open mode

 ).

,IGLIIHUHQWXQORFNLQJWLPHLVQHHGHGWREHFRQ¿JXUHGFKDQJHWKH

unlock  time  on  door  station,detail  information  refer  to  DT  system 
technical guide .

2) Door Lock Controlled with External Power

1. The external power supply must be used according to the lock.

2. The jumper must be taken off before connecting.

3. Setup the 

Unlock Mode Parameter

 for different lock types

‡

 Power-on-to-unlock type:Unlock Mode=0(by default)

‡

 Power-off-to-unlock type:Unlock Mode=1

,IGLIIHUHQWXQORFNLQJWLPHLVQHHGHGWREHFRQ¿JXUHGFKDQJHWKH

unlock time on door station,more detail information refer to DT system 
technical guide .

JP_LK

12V 300mA

Exit button

Jumper position in 2-3 

+

-

+12V

LK - 

LK+

N.O.

EB-

EB+

1 2 3

Power-on-to-Unlock type:

Power-on-to-Unlock type:

12V 300mA

Jumper position in 1-2 

+12V

LK - 

LK+

N.O.

EB-

EB+

+

-

JP_LK

1 2 3

Exit button

Power-off-to-Unlock type:

Power-off-to-Unlock type:

+

+

-

-

+12V

LK - (GND)

LK+(COM)

N.O.

EB-

EB+

Take off the Jumper

JP_LK

Cut off the line 

1 2 3

Exit button

+12V

LK - (GND)

LK+(COM)

N.O.

EB-

EB+

Take off the Jumper

+

+

-

-

JP_LK

Cut off the line 

1 2 3

Exit button

‡

Power supply:  

 

26Vdc(supplied by PC6)

‡

Power Consumption:  

1W in standby, 5W in working

‡

Unlock Power output:  

12Vdc,250mA

‡

Unlock timing:  

 

1~99s

‡

Working temperature:  

- 20ºC ~ +55ºC

‡

Dimension: 

 

316(H)x133(W)x48(D)mm 

 INSTALLATION GUIDE

DIP SWITCHES SETTING

7RWDOO\ELWVFDQEHFRQ¿JXUHGE\GLSVZLWFK7KHVZLWFKHVFDQEH

PRGL¿HGHLWKHUEHIRUHRUDIWHULQVWDOODWLRQEXWUHVWDUWLQJWKHSRZHULV

QHHGHGZKHQHYHUWKHVZLWFKHVKDYHEHHQPRGL¿HG

Bit-1 and Bit 2 is for door station ID settings. When multi door stations 
are  installed  in  the  system,  these  two  bit  must  be  set  correctly,  the 

¿UVWGRRUVWDWLRQVHWWRWKHVHFRQGRQHVHWWRWKHWKLUGRQHVHW

to 10, the fourth one set to 11. If only one door station is installed, set 
to 00.

Bit-3  is  for  single  or  double  row  button  door  station  selection.  If  the 
door station is a double row button, such as DMR21-D8, set this bit to 
0. For single row button door station,set to 1.

Bit-4  is  for  button  code  selection.  if  use  the  default  codes  for  each 
button of the door station, set to 0. If use the programmed codes, set 
to 1.(the code for each button can be programmed by software, detail 
information refer to DT system technical guide)

Bit-5 is for unlocking time quick setting. 0 is the default setting,and the 
default time is 1 second. If set to 1,the unlock time is 5 seconds(the 

XQORFNWLPHFDQEHPRGL¿HGE\GRRUVWDWLRQRUVRIWZDUH

Bit-6 is for activating the key A  and key B. Normally key A and key B 
is not activated(about the functions of key A and key B,please refer to 
DT system technical guide ),Just when it set to 1,the key A and key B 
is activated.

ON(1)

=

OFF(0)

=

ON

ON

ON

1

2

3

4

5

6

DMR21 Technical Menu

-4-

Summary of Contents for DMR21

Page 1: ...er ground LK Common contact of the relay NO Normally open contact of the relay refer to DT technical guide for Lock connection detail informations EB Exit button positive connection port EB Exit button negative connection port JP LK For electronic lock safety type setting refer to door lock connections SET 3 VZLWFKHV IRU V VWHP FRQ JXUDWLRQV CN KMB Call button module connection port CN T COIL Rese...

Page 2: ...ttach the embedded box to it The last view for all mounting Use the screws to fasten the panel Wire correctly and plug in the bus line connector Standard mounting RF CARD OFF ON OFF ON DBC4A A B C D DBC4A A B C D Impedance switch Impedance switch 100 240VAC BUS IM BUS DS PC6 AC OFF ON DBC4A A B C D Impedance switch Code 28 Code 30 Code 29 Code 31 Code 4 Code 6 Code 5 Code 7 Code 0 Code 2 Code 1 Co...

Page 3: ... 2 3 Exit button Power supply 26Vdc supplied by PC6 Power Consumption 1W in standby 5W in working Unlock Power output 12Vdc 250mA Unlock timing 1 99s Working temperature 20ºC 55ºC Dimension 316 H x133 W x48 D mm INSTALLATION GUIDE DIP SWITCHES SETTING 7RWDOO ELWV FDQ EH FRQ JXUHG E GLS VZLWFK 7KH VZLWFKHV FDQ EH PRGL HG HLWKHU EHIRUH RU DIWHU LQVWDOODWLRQ EXW UHVWDUWLQJ WKH SRZHU LV QHHGHG ZKHQHYH...

Page 4: ... Set ting a warning sound of BP will be heard and the Status indicator blinks one time per second The counting of Unlocking Time is the times that Status indicator blinks the units is second For example the Status indicator blinks for four times that means the unlocking time is 4 seconds When the door station with Camera Module is in standby 1 Press Key A and hold on for 3 seconds to enter the War...

Page 5: ...HVLUHG RX VKRXOG SUHVV FRQ UP EXWWRQ DIWHU QLVK LQSXW ting the code number each time otherwise the operation will be cancelled automatically in 10s Setting items Setting range Default value Setting code Reset all settings 1 2 3 4 00 Setting the master code 1 12 digits Valid keys 0 9 1234 01 Setting the key illumination time 10 to 99 seconds continually lit 10 seconds 02 Setting the unlock time 01 ...

Page 6: ...ange 01 99 3 Setting the key illumination time 4 Setting the unlock time 2 Setting the master code Default 1234 Default 10s Default 1s Inputting of new master code ex 4321 1 12 digits Input the setting code Inputting of code Input the setting code 1 Reset all settings 00 1234 4321 01 10 09 Input the setting code 02 Input the setting code 03 If the key illumination time is set to 00 the key illumin...

Page 7: ...set last time When the operation tone is set to 0 pressing the digital keypad will sent out a sound of beep When the operation tone is set to 1 pressing the digital keypad will blink one time Cancel all the passwords except the master code Restore the master code to default value 1 2 3 4 When the item is set to 0 press the button to cancel the input and press the button to confirm the input When t...

Page 8: ...CALL button Beep Beep Beep 11 SPK volume adjust setting Input the setting code Input the setting code 11 Inputting of code ex 5 range 0 9 5 Default 4 Unlock via password is still available even when the door station is talking When door station is talking you can enter the Master code the LED turns white upon that to activate the volume adjusting function Speaker adjustment 3 up 6 down Beep Beep B...

Page 9: ...ease the second lock the second lock need external device to support If the password length exceeds 12 digits the system will sent out the sound of beep beep beep beep and the digitals you input before will be cleared at the same time The temporary code can not be set the same as the master code The user code group1 is used to release the first lock and the user code group2 is used to release the ...

Page 10: ...he name list Press or to select name After that press to call the corresponding user 3UHVV H SDG 0RGXOH WR FDQFHO WKH FDOO This is the user interface of calling process Know that if the name list is created the resident s name will be showed on screen 3UHVV H SDG 0RGXOH WR FDQFHO WKH FDOO This is the user interface of conversation process The conversation time will be recorded 3UHVV H SDG 0RGXOH W...

Page 11: ... be asked on TFT screen This is the user interface when the right card has been read the info of Door1 open will be showed screen This is the user interface of adding card please know that the user interface of delete card or initialization is similar as the following pic ture shows Master Card Setting Power on and short out EB EB a sound of BP will be sent out and the Unlock indicator is turned o...

Page 12: ...ow the MASTER CARD ADD it will sound BP the Talk indica tor and the Unlock indicator will blink and after 10 seconds it will UHWXUQ WR VWDQGE PRGH DQG WKH IRUPDW LV QLVKHG i By PC ii By SD Card Delete by room number Input the room code it will sound BP and the Unlock indicator blinks one time all associated cards will be deleted Delete by User Card Show the User Cards which you need to delete It w...

Page 13: ...nting screw The DMR21 automatically assigns the call codes to the connected module s buttons Regardless of the structure of the call button mod ule the button numbers are listed from the top to bottom and from left to right in the case of double row buttons In the case of double row buttons Examples 01 02 03 04 05 06 07 08 RF CARD 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 09 10 11 12 13 14 1...

Page 14: ...04 06 08 10 12 14 16 10 12 14 16 18 20 22 24 26 28 30 32 RF CARD RF CARD 01 02 03 04 01 02 03 04 01 02 03 04 05 06 07 08 05 06 07 08 09 10 11 12 13 14 15 16 1 2 3 4 5 6 ON 01 02 03 04 05 06 07 08 NO Functions Call apartment 01 Call apartment 02 Call apartment 03 Call apartment 04 Call apartment 05 Call apartment 06 Call apartment 08 Call apartment 07 DMR21 Technical Menu 15 ...

Page 15: ...VZLWFKHV IRU V VWHP FRQ JXUDWLRQV Connect to CN FUN of video entry module Connect to CN KMB of video entry module Connect to CN WGN of video entry module For electronic lock safety type setting Connect to next keypad or TFT module Connect to next call button module Connect to next call button module Connect to next call button module Call button module connection port Reserved Non polarity bus lin...

Page 16: ... D16 DMR21 T4 D8 DMR21 ID S4 DMR21 ID KP INPUT INPUT OUTPUT OUTPUT CN KMB RF CARD OUTPUT INPUT INPUT CN KMB CN WGN INPUT OUTPUT INPUT CN KMB CN FUN OUTPUT INPUT CN WGN RF CARD A 1 2 3 4 5 6 0 7 8 9 B OUTPUT INPUT CN FUN DMR21 Technical Menu 17 ...

Page 17: ... A 1 2 3 4 5 6 0 7 8 9 B INPUT INPUT OUTPUT OUTPUT OUTPUT INPUT OUTPUT INPUT OUTPUT INPUT CN KMB CN FUN CN WGN RF CARD OUTPUT INPUT INPUT OUTPUT INPUT OUTPUT INPUT OUTPUT INPUT OUTPUT CN KMB CN WGN MODULE CONNECTION DMR21 Technical Menu 18 ...

Page 18: ...u want to call ODQB 3UHVV WKH UVW EXWWRQ LW ZRXOG FDOO WKH PRQLWRU LQ 8 DQG LW LV displayed Alan_1 on TFT module This section will be reserved For more details Please refer to the following section of Namelist Update By SD Card Description H QLWLRQ Calling By Buttons Calling By Namelist Calling By Keypad Module Press the call button to call corresponding monitors i Press touch sensor button to sho...

Page 19: ...t SD card to slot iii A long warning sound of BP will be sent out and the Talk indi cator is turned on iii A long warning sound of BP will be sent out and the Status indicator is turned on iii After 3 seconds all the indicators are turned on iiii After 20 seconds a long sound of BP will be sent out and all indicators are turned off It means Software update LV QLVKHG iiii After 20 seconds a long so...

Page 20: ...itch to ON as the following picture shows ii Insert SD card to slot DIP6 ON 1 2 3 4 5 6 ON INPUT CN KMB CN WGN iii A long warning sound of BP will be sent out and the Talk indi cator is turned on iiii After 20 seconds a long sound of BP will be sent out and the Talk indicator is turned off It means Namelist update LV QLVKHG CONFIGURATIONS DMR21 Technical Menu 21 ...

Reviews: