Install Your ZCSM-RP Connected Remote Pressure Monitor
The ZCSM-RP Connected Remote Pressure Monitor should be installed indoors in a dry location. Outdoor installations, direct
sunlight, or high humidity may affect the life of the product. Avoid installing the device where the device or cables may extend into
walkways or present a tripping hazard.
1.
The stainless steel pressure transmitter has a ¼” NPT male connection. Using Teflon tape for all connections, install the brass
tee onto the pressure transmitter.
Caution:
only wrench on the hex connection of the pressure transmitter. Install the 1/4” test
cock into the branch of the tee. Then install the 1/4” brass nipple into the tee. 1/2 x 1/4” and 3/4” x 1/2” bushings are provided
so the ZCSM-RP Connected Remote Pressure Monitor can be installed into 1/4”, 1/2”, or 3/4” NPT connections.
2. The Connected Remote Pressure Monitor can be installed on any existing test port in your plumbing system. Flush all dirt and
debris from the system connection before installation. Wrench on the brass fittings to install. Bleed air from system, if applicable.
3. The pressure transmitter cable should be plugged into the pressure transmitter. Align the plug to match the socket and press
firmly to insert. Use care when unplugging as the locking tab can be damaged.
4.
Once the ZCSM-RP is installed, open any system shutoff valve to provide water to the ZCSM-RP.
NOTE: Verify a Zurn Gateway is installed with 1,000 feet of your ZCSM-RP prior to completing the next step.
If a Zurn Gateway is still needed, please refer to proceeding section to request and install your Zurn Gateway to connect your
product.
5. Once the water is turned on, plug the 120vac wall adapter into a nearby power outlet. Insert the small plug into the black cable
on the ZCSM-RP. If not previously completed, register your ZCSM-RP Connected Remote Pressure Monitor. The system will
take about two minutes to boot up and start transmitting data.
Test Your Network and Register Your Products
It is recommended to test your network when installing a new Gateway. For the following steps, ensure you have the
serial number recorded from the ZCSM-RP Connected Remote Pressure Monitor.
Test Your System Network
Make sure your gateway and products communicate now that everything is installed by conducting a system connection test:
1. Plug in the ZCSM-RP Connected Remote Pressure Monitor, ensuring it is within 1,000 feet of the Zurn Gateway.
by typing in the ZCSM-RP Connected Remote Pressure Monitor product serial number.
3. Click on the ‘Validate’ button. If the system recognizes the Zurn Connected Product, it will instantly connect to the Zurn Cloud.
Register Your Products
Prior to registering, the building, floor, and room must be setup in plumbSMART™. You may then register your product in
plumbSMART™ to start receiving data.
Use the plumbSMART™ mobile application for quick registration:
1. Using the mobile app, scan or enter the serial number to register and locate each connected plumbing product as you install it.
Or register using the plumbSMART™ online porta
l:
1. Ensure you have the ZCSM-RP Connected Remote Pressure Monitor product serial number.
2. Go to
Log in to your plumbSMART™ account and select the 'Register Products' option from the
'Products' menu within the main blue navigation bar.
3. Follow the prompts to complete the registration.
4.
At this point, you can give your Zurn Connected Product a unique name and assign it to a specific building location.
5.
Finally, confirm or adjust your alert parameters based on your desired system operation.
More instructional videos can be found on the support page in the plumbSMART™ portal.