Installation

   

 

Testing

   

 Maintenance Instructions

Model 450 & 450DA

Double Check Valve Assembly (4” & 6”)

Double Check Detector Assembly (4” & 6”)

a              company

®

®

WILKINS, a ZURN  company

1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766

INSTALLATION INSTRUCTIONS

CAUTION: Installation of Backflow Preventers must be performed by qualified, licensed 

personnel. The installer should be sure the proper device has been selected for the particular 

installation. Faulty installation could result in an improperly functioning device.

WILKINS Model 450 Double Check Valve assemblies are for use on potable water lines 

where a health hazard does not exist in the event of a backflow situation.

Damage to the device could result wherever water hammer and/or water thermal expan

-

sion could create excessive line pressure. Where this could occur, shock arrestors, check 

valves and/or pressure relief valves should be installed downstream of the device.

If installation is in a pit or vault, the Backflow Preventer must never be submerged in 

water because this could cause a cross-connection. Make sure that the pit or vault always 

remains dry by providing ample drainage.

1.  Before installing a Model 450 Backflow Preventer, flush the line thoroughly to 

 

remove all debris, chips and other foreign matter. If required, a strainer should be  

 

placed upstream of the Backflow Preventer. CAUTION: Do not use a strainer in  

 

seldom used emergency waterlines such as fire lines.

2.  Provide adequate space around the installed unit so that the test cocks will be  

 

accessible for testing and servicing.

3.  Install valve at least 6 inches above surrounding flood level.

4.  Always consult local codes for installation methods, approvals and guidance.

PLACING THE DEVICE IN SERVICE

1.  Start with both shut-off valves closed. 

Slowly open the inlet shut-off valve until the 

backflow preventer is completely pressur

-

ized.

2.  When the unit has been pressurized, 

vent  any  trapped  air  by  slightly  opening 

each of the four test cocks.

3.  Slowly open the downstream shut-off 

valve. The Model 450 Double Check Valve 

assembly is now in service.

4.  After the Model 450 has been prop-

erly installed, test the device (see “TEST 

PROCEDURES”).  If  the  device  fails  the 

test,  remove  the  first  and  second  check 

valves  and  thoroughly  flush  the  device. 

Clean rubber and seats of all debris and 

place unit back in service.

(Patent No. 5,913,331)

 

PROTECTIVE

ENCLOSURE

6"  MIN.

WILKINS VALVE

 SETTER  MJFS

DIRECTION OF FLOW

INDOOR INSTALLATION

Indoor  installation  is  preferred  in  areas 

that are subject to freezing conditions. All 

the basic installation instructions apply to 

such installations.

OUTDOOR INSTALLATION

The Model 450 Backflow Preventer may be installed outdoors only if the device is 

protected against freezing conditions. Exposure to freezing conditions will result in 

improper function or damage to the device. The installation location must be kept above 

32°F. All the basic installation instructions apply.

TYPICAL HORIZONTAL ORIENTATION

Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects 

or other reproductive harm. 

Содержание WILKINS 450

Страница 1: ...e adequate space around the installed unit so that the test cocks will be accessible for testing and servicing 3 Install valve at least 6 inches above surrounding flood level 4 Always consult local codes for installation methods approvals and guidance PLACING THE DEVICE IN SERVICE 1 Start with both shut off valves closed Slowly open the inlet shut off valve until the backflow preventer is complete...

Страница 2: ...valve 1 after gauge reading stabilizes and water stops running out of test cock 3 5 Close all test cocks open shut off valve 1 and remove test equipment TEST NO 2 TIGHTNESS OF 2 CHECK VALVE REQUIREMENT The static pressure drop across check valve 2 shall be at least 1 0 psid If test cock 4 is not at the highest point of the check valve body then a vertical tube must be installed on test cock 4 so t...

Страница 3: ...he back of the check assembly See Check Assembly illustra tion Separate the seal retainer from the assembly to expose the seal ring 8 Inspect the seal ring for cuts or embedded debris If the reverse side of the seal is unused the seal ring can be inverted and used temporarily until a new seal is obtained Inspect seat o ring and replace if cut or damaged in any way 9 Inspect valve cavity and seatin...

Страница 4: ...c testing according to WILKINS specifications and prevailing governmental industry standards and codes and upon following these installation instructions Failure to do so releases WILKINS of any liability that it might otherwise have with respect to that device Such failure could also result in an improperly functioning device PROBLEM POSSIBLE CAUSES CORRECTIVE ACTION 1 LEAKING CHECK VALVES 1 Debr...

Отзывы: