FV696  Rev. B   07/29/20

Page 8    

CALIBRATION INSTRUCTIONS FOR ZEMS-IS-W1

1. 

Obtain a target. SEE FIGURE on the right. 

2.  PRESS and HOLD button for 10 seconds or until the 

LED turns solid.  (Unit will blink four times and flush 

once while button is being held.)

3. 

RELEASE finger after LED turns solid.

4.  PRESS and HOLD button when LED starts blinking.

5. 

RELEASE finger when LED turns solid.

6.  Set target at desired distance (no less than 18” from 

sensor face) and verify NO other objects are in view of 

sensor face.

7. 

Keep target steady (Unit will blink while calibrating.)

8. 

After 30 seconds, calibration ends with a fast double 

blink or a solid LED for 5 seconds.

9. 

IF THE LED REMAINS SOLID FOR 5 SECONDS 

AFTER CALIBRATION, the calibration was NOT 

successful.  REPEAT STEPS 2-8.

10. 

For closet installations continue to “VERIFY 

CALIBRATION FOR CLOSET INSTALLATIONS”.

Verify Calibration for Closet Installations

1. 

Stand outside closet stall and close door and verify that 

sensor does not see stall door.  If LED blink/flashes, 

recalibrate to a shorter range.

2. 

Slowly open door to closet stall while looking at ZEMS-

IS-W1 sensor.

3.  If LED blinks while door is opening, recalibrate to a 

shorter range.  FAILURE TO DO SO WILL RESULT IN 

“GHOST”   FLUSHING.

The  ZEMS-IS-W1  is  factory  set  to  accommodate  most 

closet and urinal installations.  If this factory setting does not 

accommodate your specific environment, follow the  steps 

below  to  customize  your  range  settings  for  your  specific 

ZEMS-IS-W1 model.

Activating the Motor Actuator with the Sensor

 

To activate the motor actuator with the sensor, simply place 

a target in front of the sensor.  A single red light will flash 

indicating the sensor has recognized the target.  If the 

target stays in view for eleven seconds, two flashing red 

lights will occur.  This indicates that the target has been 

in view for the required time and, upon leaving the view, a 

signal will be sent to the motor actuator to flush the flush 

valve.  NOTE: If the target does not stay in view for the 

required eleven seconds, a flush will not occur.

Customized Sensor Range Setting

Recommended brown 

cardboard target

(16” x 16”)

Recommended Distance Settings

Urinal

22” from Sensor Face

Water Closet

6”-8” beyond front lips of toilet bowl

Calibrating to a distance less then 18” from sensor face 

may result in false activation.

• 

Do not use any abrasive or chemical cleaners to clean the flushometer.

• 

The suggested cleaning of chrome plated surfaces is simply to clean them with mild soap and water, then dry. Commercial 

cleaning compounds are never recommended.

• 

Upon cleaning other areas of the restroom, be sure that the sensor lenses are protected from other cleaning chemicals/

solvents to prevent potential damage to the sensor and/or electronics.

• 

Valves used in installations subject to shut down because of cold and freezing conditions should be maintained in the following 

manner:  After the main supply has been shut off and the water drained from the system, remove the stop valve cap and stop 

valve internals to allow the water to drain from the flush valve itself.

Care and Cleaning Instructions

Содержание plumbSMART ZEMS-IS Series

Страница 1: ...nsequential damages The sole and exclusive remedy shall be limited to the replacement of the defective goods Before installation and use the purchaser shall determine the suitability of the product for his intended use and the purchaser assumes all risk and liability whatever in connection therewith Where permitted by law the implied warranty of merchantability is expressly excluded If the product...

Страница 2: ...This Page Intentionally Left Blank ...

Страница 3: ...In the event of valve failure fixture must be able to handle a continuous flow Be certain power is off to prevent damage to electrical components and or personal injury Features Zurn s AquaVantage TPE Diaphragm Clog resistant triple filter or linear filter by pass Chloramine resistant Dual seal Zurn s MetroVantage Piston Clog resistant by pass Chloramine resistant Proprietary dezincification resis...

Страница 4: ...cept any interference received including interference that may cause undesired operation The following information refers to Zurn Smart Connected Products types W1 This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference intended for us...

Страница 5: ...nal Flush Connection for Water Closet Hand Drill Measuring Tape 1 3 4 Bit Sweat Solder Connection with Cast Wall Flange Control Stop with Vandal Cap optional with AquaFlush Endpoint ZEMS IS W1 Actuator Valve Body Parts List Required Tools Smooth Jawed Wrench Flat Head Screwdriver ...

Страница 6: ...th items over water supply pipe Press wall escutcheon flush against finished wall and tighten set screw with hex wrench supplied to secure it in place Using a flat head screwdriver turning counterclockwise flush supply line by opening the control stop Turning clockwise will close the control stop 2 Gallon 1 Install control stop assembly by threading it onto water supply pipe and tightening with a ...

Страница 7: ...Determine the length of vacuum breaker tube required to join the flush valve and fixture spud and cut if necessary Slide the tube nut spud nut slip gasket rubber gasket and spud escutcheon over the vacuum breaker tube and insert tube into fixture spud Hand tighten tube nut to valve body and hand tighten spud nut onto fixture spud Adjust the valve assembly for plumb Tighten fixture spud nut vacuum ...

Страница 8: ...t through wall opening as shown below 3 1 8 13 8 Center line of Flush Valve Height of Stop Valve 1 3 4 Hole Through Wall Top Of Fixture Connect power and data cables from ZEMS IS W1 actuator to power and data extension cables from Endpoint through the hole Install actuator escutcheon to the actuator pipe with setscrew toward actuator Do not tighten setscrew at this time With escutcheon loose and h...

Страница 9: ...y be performed by a licensed electrician 3 Connect power cord with Wago connector as outlined on the left See P6000 HW6 installation manual for detailed instruc tions 4 Each pair of endpoint and actuator should be wired in parallel as shown in the diagram below and should be connected us ing the optional P6000 MJ Mini Junction Box or crimp lugs 5 For installing a single pair of endpoint and actuat...

Страница 10: ...ur specific ZEMS IS W1 model Activating the Motor Actuator with the Sensor To activate the motor actuator with the sensor simply place a target in front of the sensor A single red light will flash indicating the sensor has recognized the target If the target stays in view for eleven seconds two flashing red lights will occur This indicates that the target has been in view for the required time and...

Страница 11: ...pped below minimum operating range Steps should be taken to increase the line pressure Water splashes out of fixture Supply volume is more than is necessary Adjust downward on control stop Lime accumulation on vortex or spreader holes of fixture Remove the lime build up Flush is not considered quiet Control stop is not adjusted for quiet operation Adjust the control stop for quiet operation keepin...

Страница 12: ... restricted access Contact organization IT department No lights are flashing Gateway is not powered Power gateway Portal High daily use alerts Usage spiked Adjust threshold possibly move to portal area Endpoint is not appearing on portal Endpoint was not registered on plumbSMART Register device in plumbSMART Device is not communicating alert See endpoint troubleshooting See endpoint troubleshootin...

Страница 13: ... 2 4 13 P6000 EUA ULF RK P6000 EUA WS1 RK P6000 EUA WS RK Control Stop Repair Kit and Parts Product No Control Stop Repair Kit for 1 and 3 4 Items 14 20 P6000 D SD Seal Seat for 1 and 3 4 Items 14 P6000 D42 Sweat Solder Connection P6000 YBA Vandal Resistent Cover Item 23 P6000 VC Repair Part Inside Part Product No Urinal Relief Valve Item 6 P6000 EU13 Closet Relief Valve Item 6 P6000 EC13 1 Valve ...

Страница 14: ...r Kits Product No Outside Cover Items 8 P6200 LL Outside Cover O Ring Item 7 P6200 L12 Main Seat Item 5 P6000 S 30 Water Closet Kit 1 28 GPF Items 5 6 P6200 EC HET Water Closet Kit 1 6 GPF Items 5 6 P6200 EC WS1 Water Closet Kit 3 5 GPF Items 5 6 P6200 EC Urinal Kit 0 125 GPF Items 5 6 P6200 EU ULF Urinal Kit 1 0 GPF Items 5 6 P6200 EU WS1 Urinal Kit 1 5 GPF Items 5 6 P6200 EU Adjustable Tailpiece...

Страница 15: ...This Page Intentionally Left Blank ...

Страница 16: ...TRIES LLC 511 W Freshwater Way Milwaukee WI U S A 53204 Ph 1 855 ONE ZURN Fax 919 775 3541 In Canada ZURN INDUSTRIES LIMITED 7900 Goreway Drive Unit 10 Brampton Ontario L6T 5W6 Ph 905 405 8272 Fax 905 405 1292 Rev B Date 07 29 20 C N No 142895 Prod Dwg No FV696 ...

Отзывы: