Page 17
HYDRANTS
ZURN INDUSTRIES, LLC
Specification Drainage Operation , 1801 Pittsburgh Avenue, Erie, PA 16502, 855.663.9876 Form No. ZMKTG210-15, 7/18
ENGINEERING SPECIFICATION:
ZURN Z1310 Exposed Ecolotrol anti-siphon automatic
draining wall hydrant. Complete with non-freeze integral backflow pre ven ter, bronze
casing, all bronze interior parts, non-turning operating rod with free-floating compres-
sion closure valve, replaceable bronze seat and seat washer, and combination 3/4” [19
mm] female or 1” [25 mm] male straight IP inlet. Stainless steel face with operating key.
Z1310 ECOLOTROL WALL HYDRANT –
Exposed, Non-Freeze, Anti-Siphon, Automatic Draining
Inlet Descriptions
Standard
-34FS
-34UN
Z1310 Ecolotrol Wall Hydrant
The Z1310 Ecolotrol is an exposed, automatic draining, non-freeze, anti-
siphon wall hydrant designed for commercial applications such as office
buildings, institutions, hospitals, malls and retail outlets, and schools.
Hydrant Features
•
Certification
– IAPMO
®
listed.
Approved under ASSE standard 1019-A
(3/4” [19 mm] connection).
•
Integral Anti-Siphon Vacuum Breaker/Backflow Preventer –
Unique
design utilizes an internal Equa-Balance
®
seal to prevent contamin a-
tion of the potable water supply through back siphonage. The use of an
additional hose-connection vacuum breaker with ASSE 1011 approval
is not necessary.
•
Valve Seat –
Removable bronze valve seat with circular seating surface.
•
Valve –
One-piece assembly, replaceable, free-floating compression
closure valve plunger operates the water flow and drainage with a maxi-
mum of two and one-half (2-1/2) turns. No adjustments are necessary.
•
Casing –
Threaded brass pipe nipple.
•
Operating Screw –
Chrome-plated brass.
•
Operating Rod –
3/8” [10 mm] solid brass.
•
Faceplate –
Constructed of type 304 stainless steel with brush finish.
•
Modular Installation –
Hydrant may be installed in a horizontal or
vertical orientation. Fits standard modular brick course when installed
horizontally.
•
Drainage –
Through circular drain ports of the nozzle.
•
Operating Pressures –
Minimum running pressure 8 psi. Maximum
static pressure 125 psi.
•
Temperature Range –
Minimum 33°F. Maximum 130°F.
®
SUFFIXES
–PB
Polished Bronze Face
–RA2
12” [305 mm] Replacement Rod Assembly with Repair Kit (-RK)
–RA4
24” [610 mm] Replacement Rod Assembly with Repair Kit (-RK)
–RK
Hydrant Parts Repair Kit
–SB
Statuary Bronze Face
(Specify light, medium, or dark finish.)
–WC
Wall Clamp
–34FS
3/4” [19 mm] Solder Female Inlet Adapter
–34UN
3/4” [19 mm] IP 90° Inlet Elbow with Union Nut
OPTIONS
Wall Thickness
4” 6” 8” 10” 12” 14” 16” 18” 20” 22” 24”
Inches [mm]
[102] [152] [203] [254] [305] [356] [406] [457] [508] [559] [610]
Overall Length*
6
3
⁄
4
” 8
3
⁄
4
” 10
3
⁄
4
” 12
3
⁄
4
” 14
3
⁄
4
” 16
3
⁄
4
” 18
3
⁄
4
” 20
3
⁄
4
” 22
3
⁄
4
” 24
3
⁄
4
” 26
3
⁄
4
”
Inches [mm]
[171] [222] [273] [324] [375] [425] [476] [527] [578] [629] [679]
Approx. Weight
5 5 5 8 8 8 11 11 14 14 14
Lbs. [Kg]
[2] [2] [2] [4] [4] [4] [5] [5] [6] [6] [6]