background image

FV62  Rev. D   11/14/18
Page 6    

1. If the white connector is not fully accessible then the 

sensor module must be removed from the case in order 
to reassemble the solenoid connector to the sensor 
connector.

2. Remove the battery cover (Item #10) from the RetroFlush 

sensor assembly (Item #9).

3. Remove the battery case (Item #15) and disconnect from 

the sensor.

4. Remove the sensor module (Item #12) held in place by 

two screws (Item #13) and rubber plug (Item #14).

5. Lightly lubricate the solenoid O-ring seal with silicone 

grease provided to prevent damage while reassembling 
the unit. Insert the solenoid (Item #7) into the housing 
and install the solenoid retaining clip (Item #8). When 
installed properly, the end of the solenoid is free to rotate. 

Notes: Be careful not to crimp the battery wires while 
inserting the solenoid into the housing. Also, be sure 
the blue and gray wires of the solenoid valve extend 
into the sensor module cavity of the housing (Item #9).

6. Connect the sensor module blue and gray wires to the 

solenoid valve blue and gray wires and reinstall the 
sensor module. 

Note: Be very careful not to crimp the 

wires when reinstalling the sensor module. Replace 
the two screws (do not over tighten) and rubber plug 
holding the sensor module in place.

7. Replace the battery pack and reconnect to the sensor.
8. Continue with Step 3 and beyond under “Installing The 

New Solenoid” on reverse side of this page.

ZR Flush Valve/ZRK Retrofi t Kit

Solenoid Replacement Instructions

Special Note On #9 – Removing Old Solenoid Valve

Содержание AquaSense AV ZR Series

Страница 1: ...provided we are notified in writing of such defect and the goods are returned to us prepaid at Sanford NC with evidence that they have been properly maintained and used in accordance with instructions We shall not be responsible for any labor charges or any loss injury or damages whatsoever including incidental or consequential damages The sole and exclusive remedy shall be limited to the replacem...

Страница 2: ...nut with a wrench Do not turn water on until batteries are inserted see 8 2 Prior to inserting the flush valve tailpiece into stop valve be certain that the o ring seal is located in o ring seal groove at the end of the tailpiece and the locking nut and locking snap ring are located as shown Care should be taken not to damage the o ring when inserting the tailpiece into the stop valve If lubricati...

Страница 3: ...he final setting for urinals should be such that the fixture will not overflow when the valve is actuated twenty times in succession The stop cap screw cover should be replaced after final adjustments have been made Sensor Range Adjustment The range is factory set for urinal or closet applications If necessary the sensor range can be adjusted Pressing the reset button will initiate a ten minute se...

Страница 4: ...ent For the first ten minutes of operation the red light will flash when an object is detected 2 Low Battery Indication When the batteries have reached the caution level the red light will flash when an object is detected 3 Abnormal Reflection Indicator When a reflective surface is present for longer than 30 minutes the red light will flash indicating that an object is being continuously detected ...

Страница 5: ...age while reassembling the unit Insert the solenoid Item 7 into the housing and install the solenoid retaining clip Item 8 When installed properly the end of the solenoid housing is free to rotate Note Be careful not to crimp the battery wires while inserting the solenoid into the housing 3 Reinstall the RetroFlush sensor assembly Item 9 onto the flush valve using a wrench Be sure the solenoid inl...

Страница 6: ...Item 8 When installed properly the end of the solenoid is free to rotate Notes Be careful not to crimp the battery wires while inserting the solenoid into the housing Also be sure the blue and gray wires of the solenoid valve extend into the sensor module cavity of the housing Item 9 6 Connect the sensor module blue and gray wires to the solenoid valve blue and gray wires and reinstall the sensor ...

Страница 7: ...lume Control 3 5 GpF 3 PR6000 EU25 WS Low Consumption Urinal Volume Control 1 6 GpF 3 PR6000 EU25 WS1 Diaphragm PR6000 E15A Sensor Module Replacement Kits Product No Solenoid Valve Replacement Kit 8 9 10 PR6000 M Sensor Lens Kit 12 PR6000 SC High Volume Sensor 13 PR6000 SH Low Volume Sensor 13 PR6000 SL Battery Holder with Connecting Cable 15 16 PR6000 MB Metal Housing 11 PR6000 MH Vandal Resistan...

Страница 8: ...e or chemical cleaners to clean flush valve as they will dull the luster and attack the chrome or special decorative finishes Use only mild soap and water then wipe dry with a clean cloth or towel While cleaning the bathroom tile and floor the flush valve and electronics should be protected from splattering of water cleaner acids and cleaning fluids that can damage the sensor flush valve Problem C...

Отзывы: