TROUBLESHOOTING

MATERIALS

Body  

 

Bronze ASTM B 584

 

 

UNS C84400, nickel plated

Internal brass  

Brass ASTM B-16 UNS C36000

Piston    

Polysufone

Guide Tube  

Noryl GFN2

Spring & Screen   300 Series Stainless Steel

Seals  

 

Viton

Checks    

Noryl GFN2

 

MAINTENANCE

SERVICING THE STRAINERS

The strainers on the inlet supplies can be serviced by loosening the 

union nuts, removing the valve from service and clean the screens 

thoroughly with water after disassembly. Where water quality is a 

concern it may be necessary to install additional line strainers.

SERVICING THE CHECK VALVES

The check valves can be serviced by removing them from the body. 

Flush the check valves thoroughly with water removing debris 

from the seat and seat washers. Reinstall the check valve by 

pushing them into the body flush to the body, spring first. Make 

sure that the poppet and seat washer is facing you.

OPERATION

The valve internals themselves cannot be serviced. If the valve fails 

it must be replaced. The function of the valve can be checked by 

measuring the temperature of the water at the outlet nearest to 

the valve. If the temperature is /- 1.8°C of the initial set 

temperature, the valve is functioning correctly. If the temperature 

has changed by more than +/- 1.8°C it is likely due to a build up of 

debris in the stainers or a change in the supply condition.

ZURN AUSTRALIA

49 LAKESIDE DRIVE BROADMEADOWS VIC 3047  

PHONE: 1300 00 ZURN

EMAIL: [email protected]  

               Removing Cap

  

Temperature Adjustment

FLOW RATES (GPM

)

PRESSURE LOSS (PSIG)

 

0

20

40

60

5

0

10

15

20

138

276

414

0.

0

3

.6

0

3

.95

1.3

PRESSURE LOSS (kpa)

 

FLOW RATES (l/s

)

MODEL ZW1070 (STANDARD & METRIC)

FLOW CHARACTERISTICS

PROBLEM

CAUSE

SOLUTION

The desired mixed water temp. cannot be

obtained or valve is difficult to set 

Hot and cold supplies are reversed, valve 

is full of debris or strainers are fouled

Re-fit valve so H & C are correct, flush valve 

with water and clean strainers

Mix. Temperature is unstable

Strainers are fouled or fluctuating supply 

pressure

Clean strainers and Install PRV's on 

H & C inlet supplies

Mix T

emperature changing over time

Fluctuating supply pressures or strainers 

are full

Install PRV's and clean strainers

Valve is set incorrectly

Adjust mix. Temperature to 35°C - 46°C

No flow from the valve outlet

Hot or Cold water supply failure or strainers 

are fouled

Restore inlet supply & check mix. 

Temperature and clean strainers

Flow rate reduced or fluctuating

V

alve or inlet fitting fouled by debris

Check valve and inlet fittings for blockage

Mixed water temp. too Hot or Cold

Valve has been tampered with, valve 

incorrectly set, or inlet temperatures are 

not within specified limits

Re-adjust to required set temp. to ensure 

inlet temperatures are within specified 

limits

Mixed water temp. does not change when 

the temp. adjuster is moved

Hot and Cold supplies are reversed

Refit the valve to correct Hot and Cold

Hot water flows into the cold water system 

or vise versa

Check valve is fouled

Clean strainers and remove debris

Valve is noisy

Water velocity is too high

Reduce water velocity

Either full Hot or Cold water flowing