Commissioning the field level
LM-CIRIA operating and commissioning manual 2.0 | 06. 2012 | en
113
Assigning a waiting time
Figure 176:
NEXT SCENE
settings level
–
Start point:
NEXT SCENE
settings level
1. Select
NEXT STEP
.
=
WAITING TIME
settings level appears.
Figure 177:
WAITING TIME
settings level
2. Select
MINUTES
.
=
MINUTES
illuminates.
3. Run your finger along the touchring until the desired number appears.
4. Select
SECONDS
.
=
SECONDS
illuminates.
5. Run your finger along the touchring until the desired number appears.
6. Select
SAVE
to save the settings.
=
The message
SAVED
briefly appears.
=
Waiting time is saved.
7. Select
NEXT STEP
to switch to the
NEXT SCENE
settings level.
8. To configure more scenes, start in the
NEXT SCENE
settings level and select the next scene.
9. To exit the scene sequence configuration, configure the stop scene (see Section
.
Notes
•
Settings are only saved if
SAVE
is selected.
•
Selecting
SAVE
automatically saves all values displayed on the touchscreen.
•
To switch to the
NEXT SCENE
settings level directly (without saving), select
NEXT STEP
.
Parameter
Value range
MINUTE
0 – 59
SECONDS
0 – 59
Table 74:
WAITING TIME
setting options