ZXG10 iBSC Hardware Installation Guide
You can adjust the height H of the base by adjusting the bolt (No.3 shown in the figure).
Applicable scope for different bases is shown in
Table 5-1 Applicable Scope
Type
Scope
Type A
Height of the antistatic floor: 155~210 mm
Type B
Height of the antistatic floor: 210~310 mm
Type C
Height of the antistatic floor: 310~510 mm
The minimum height of raised floor is 155 mm.
3.
Washer. For a rough ground surface, the washers provided by ZTE may be used
between the base and the ground for partial adjustment. The washer has two heights:
1~2 mm, as shown in
.
Figure 5-5 Washer Specifications
1.
1 mm washer
2.
2 mm washer
4.
Cabinet foot, its structure and position shown in
.
Figure 5-6 Foot Structure and its Position
1.
Cabinet
2.
Foot
3.
M16 Bolt
4.
Fastening Nut
5.
Height-adjusting nut
6.
Insulating rubber
washer
5.
Pressure plate, used to fix cabinet foot and the base, as shown in
5-6
SJ-20110531095035-004|2011-10-28 (R2.0)
ZTE Proprietary and Confidential