ZXDU58 B900 Product Description
S.N.
Alarm Name
Alarm Level and Output Relay
Alarm Description
11
SMR Over-Iout
Default level: Major
Default relay: A2
The output current of the rectifier is higher
than the threshold, and the rectifier stops
output.
12
SMR Fan Fault
Default level: Major
Default relay: A2
The fan of the rectifier is faulty.
13
SMR PFC Fault
Default level: Major
Default relay: A2
The PFC (Power Factor Correction) circuit of
the rectifier is faulty.
14
SMR Over-Vin
Default level: Major
Default relay: A2
The input voltage of the rectifier is higher than
the threshold.
15
SMR L.Vin Off
Default level: Major
Default relay: A2
The input voltage of the rectifier is lower than
the threshold.
16
SMR H.T. Off
Default level: Major
Default relay: A2
The temperature of the rectifier main radiator
is higher than the threshold, and the rectifier
stops output.
17
SMR Env.H.T.Off
Default level: Major
Default relay: A2
The environment temperature of the rectifier
is higher than the threshold, and the rectifier
shuts down for protection.
18
SMR Env.H.T.
Default level: Minor
Default relay: 0
The environment temperature of the rectifier
is higher than the threshold, and the rectifier
output is encountering linear load shedding.
19
SMR L.Vin
Default level: Minor
Default relay: 0
The input voltage of the rectifier is lower than
the threshold, and the output power of the
rectifier is derated.
20
SMR Fuse Broken
Default level: Major
Default relay: A2
The output fuse of the rectifier is blown.
21
SMR CommFail
Default level: Major
Default relay: A2
The communication between the rectifier and
the monitoring unit is interrupted.
22
DC Under-Volt
Default level: Minor
Default relay: A6
The DC output voltage is lower than
DC
UnderVolt.
23
DC Over-Volt
Default level: Minor
Default relay: 0
The DC output voltage is higher than
DC
OverVolt.
24
DC Loop Broken
Default level: Major
Default relay: A4
The load loop is not connected.
25
Batt.Loop Brk.
Default level: Major
Default relay: A4
The battery loop is not connected.
26
Bat Under-Volt
Default level: Major
Default relay: A6
The battery voltage is lower than
Batt.UnderVolt
.
6-2