12
PROCEDURE OF SETTING PARAMETERS BY MEANS OF PUSH-BUTTONS
For simple programming of required operating parameters, the control unit is fitted with four push-buttons:
MENU, P, O, C
and three signal lamps.
Yellow
Red
Green State
-
-
-
System without feeding
-
-
lit on
Everything OK – working regime
(remote, local or switched off control)
-
blinking
lit on
Error or warning – working regime
(remote, local or switched off control)
lit on
-
lit on
Enter or exit of Setting of parameters by means of push-buttons
or Setting of parameters by means of PC
blinking
-
lit
on
blinking
blinking
lit on
Setting of parameters by means of push-buttons
blinking blinking
lit
on
In adjustment, follow the paragraphs “VERIFICATION of APPARATUS FUNCTION And its LOCATION”,
“fitting on VALVE” and “ADJUSTMENT of ACTUATOR with VALVE” of these instructions.
For safety reasons, the system is delivered in the state of induced error of Calibration when the functions are
limited in order to reduce the risk of damage to the actuator by wrong wiring.
Record of position CLOSED, OPEN and AUTOCALIBRATION
– The actuator must be adjusted in such a way that the recorded position would switch off the actuator before it is switched
off by torque. For tight closure, the torque relay for torque Closed is only connected into the control circuit. The actuator
can be shifted either manually or electrically. The actuator in version CONTROL can be started from menu MOTOR in
program DMS2. In this case, the actuator does not react to the set position and can only be stopped by the torque relay.
In controlling from menu MOTOR, no torque may be induced. The torque must be left manually.
If, during adjustment, the torque is reached in the end-limit position, the torque must be left by means of a hand wheel.
–
The actuator is set to position Closed and position Closed is stored by long pressing of push-button C
(without
entering the Menu).
–
The actuator is set to position Open and position Open is stored by long pressing of push-button O.
–
The calibration routine is started by means of push-button P
(in remote control)
that, in the three-position regulati-
on, will measure actual inertial masses of the system and store them into the memory of the control unit. In the
two-position regulation, pressing of push-button P only cancels the error of Calibration.
–
In recording the end-limit positions, signalling relays and the position transducer are also set.
– In case the actuator stroke is to be increased and the switching off is set to “from position”, the actuator will switch off
during shifting in position O or 100 %. To further change the position, press C or O, and, while keeping it depressed, the
actuator can be further shifted. After required position is reached, it is stored to memory by pressing push-button C or O.
Parametr – Parameter
Změna – Change
Chyba – Error
Přístup – Access
Setrvačnost
(0,1 %)
– Inertia [0.1 %]
Setr. Doběh
(0,1 s)
– Inertial run-out [0.1 s]
Necitlivost
(%)
– Insensitivity [%]
NE – NO
¼ÈÆ
ÉÈоË
ÍÈËÄ
ºÂÇ
ž½ª ž½« ž½¬
ƾÇÎ
É
È
¼
Push-buttons and signal lamps LED on control unit DMS2.ED.S and DMS2.ED.S90
Colours of diodes:
LED1 – yellow
(menu number)
LED2 – red
(parameter value)
LED3 – green
Содержание MODACT MO EE 52 120