5
2.
O/B
and
HP
jumpers
(B&C)
should both be on one pin or removed, for GE operation.
3.
PRIORITY
jumper
(D)
should be on one pin.
Note: If the Priority opposing zone strategy is to be used, this jumper position will be changed
after the initial system start-up is completed.
See Advanced Feature Configuration.
4. Set the power switch
(E)
to
ON
.
5. Set the
NIGHT DAY
switch
(L)
to the
DAY
position.
6. Set the fan jumper
(M)
to
AUTO
for intermittent operation or
ON
for constant ON operation in
the Occupied mode.
7. Place the
LOCK
–
UNLOCK
switch
(P)
in the UNLOCK position.
8. Place the
TIME/TEMP
jumper
(Q)
on the middle and upper pins to control Y2 and W2 staging
on run time and supply air temperature.
GEN II Gas Electric Advanced Feature Configuration
Gas Electric Capacity Control - Cool and Heat cut-out temperature adjust
The factory setting for the Cool and Heat cut-out temperatures is 45°- 145°F (7°- 62°C). This can
be easily changed with the following procedure:
1.
Cool cut-out temp
– Press the DN button
(N)
;
“C” will be displayed and then the cut-out
temperature.
2. LOWER – Press the DN button; after the “C” is displayed, continue to hold the DN button until
the desired temperature is displayed; then release.
NOTE: The controller will not change the Cool cut-out lower than 40°F (4°C).
3. RAISE – Press the DN button; after “C” is displayed, immediately release the DN button and
press the UP button. Hold until the desired temperature reading is displayed, and release.
4. Press the DN button to verify the new cool cut-out temperature.
Heat cut-out temperature
- Press and hold the UP button; after the “H” is displayed, use the same
procedure as above to raise or lower the displayed temperature.
Electric Heat - Fan Configuration
EH
jumper
(A)
is installed by the factory on one pin for normal gas heat operation where the fan is
controlled by the HVAC system fan control. When a fan output is required from the
GEN II
controller on a call for heat, place the
EH
jumper over both pins for several seconds and then
remove. Place the jumper tab on one pin.
2
nd
Stage Heat and Cool Cut-in Configuration
The
GEN II
controller is set up at the factory to stage Y2 and W2 cut-in operation based on a 3-
minute time delay and supply air temperature. This is done with a jumper which is placed on the
middle and upper pins on TIME/TEMP
(Q),
and the cut-in delay set at 03 (3 min) in the controller
program. The cut-in temperatures are fixed in the controller program at 57°F (13°C) and higher for
Y2 and 120°F (48°C) and lower for W2. The Y2 and W2 cut-in delay sequence can be field
adjusted (see below).
Adjust 2
nd
Stage Cut-in Time Delay
1. To increase the Y2 and W2 cut-in delay, press and hold the SET and DN buttons
(N)
simultaneously. When 03 appears in the display, release the buttons and immediately press
the UP button and hold until the desired delay time is displayed, and release. The time delay
is fully adjustable from 3 - 20 minutes. To verify the change, press and hold the SET and DN
buttons simultaneously until the delay time is shown, and release.