background image

FORM 320251-0803 

©2007 ZONEFIRST

 

3

 

The case has openings in the rear of the case as well as the side 
for all wiring.  Wiring can come from the back as well as the side 
in order to make a neat installation.   

 

OPERATION 

The H32P can be controlled by conventional single stage or 
heat pump thermostats.   Each thermostat can then call for 
heating, cooling or the fan.  When a thermostat calls the panel 
will keep open the damper to the calling zone, if not already 
open, close the dampers to the zone(s) not calling and activate 
the appropriate HVAC equipment.  When opposite calls exist 
for both heating and cooling the panel will allow the zones to 
automatically switch between the modes.  When all zones are 
satisfied the panel then looks for individual fan calls from any 
zone and controls the dampers based on these calls as well.  
When all zone thermostats are not calling for heating, cooling or 
the fan all dampers will return to a normally open position.   
Once a call for either heating or cooling is made the panel will 
open the damper(s) to the zone(s) calling, close the damper(s) 
to those zones not calling, activate the appropriate controls for 
heating or cooling, whichever is being called and not accept any 
calls for the opposite mode.   
 
Any calls for the opposite mode will be locked out until the 
initial mode is either satisfied or a period of time has elapsed 
that is sufficient for the first mode to satisfy, a maximum of 20 
minutes.  A unique sequence determines the time the unit has 
been running or needs to continue to run in order to adequately 
provide conditioning for each mode.  If a particular mode has 
already been calling for 20 minutes or longer and an opposite 
call comes in the H32P will immediately drop the mode, enter 
the purge mode in order to dissipate the conditioned air into the 
zones calling before switching over to provide the new 
conditioning call to its zones.   
 
When using the H32P to control two stage heating, the second 
stage is controlled based upon time after the first stage call from 
the thermostat.  When any zone calls the panel’s built-in timer 
begins and after the set period of time elapses the H32P will 
also activate the W2 for second stage heating.   The Second 
Stage Timer is adjustable between 2, 4, 8 or 16 minutes after the 
first stage calls.  Once the second stage is on, it will continue to 
run until the first stage is satisfied.   
 
Once all zone thermostats are satisfied for heating and cooling, 
the H32P can now accept Fan calls allowing Continuous Air 
Circulation(CAC) in those zones where the thermostat’s Fan 
Switch is set to ON.  These zone dampers will be Open while 
the dampers to the zones where the Fan Switch is set to AUTO 
will be CLOSED.   
 
When all zone thermostats are satisfied for both Heating and 
Cooling, and all Fan switches are set to AUTO position, the 
HVAC unit will be off and all zone dampers will return to a 
normally open position.  Once a zone calls for heating, cooling 
or fan, the dampers to the calling zones remain open and the 
dampers to the zones not calling will close.   
 

Set-Up for Various HVAC Equipment 

The H32P is factory set for conventional heating and cooling 
operation.  The panel only needs to be configured when using 
with an electric furnace or heat pumps.  
 
 
 
 
 

Most all of the panel configuration is done by setting the DIP 
switches in the top right of the panel.  Other functions come by 
wiring for specific applications.  Below is shown the most typical 
settings.  Review each function for you application.     
 

SYSTEM – G/E OR HP 

This switch sets the HVAC Output 

operation.  In G/E the Y1 makes as a Cool call and W1 as a 
Heat call.  In HP position Y1  makes as the compressor call for 
both heating and cooling.   

HP Type – CONV or FF 

– This switch is used to determine the 

equipment output when the System switch is set to HP , this 
switch determines if the output will be for a conventional heat 
pump with electric back-up heat or fossil (dual) fuel mode.   

FAN IN HEAT – YES or NO

 – This switch will activates the Fan 

on a call for Heat in the Yes position.  In Off, the heating unit 
must activates the fan when the heat is called.  

 

FAN PURGE – YES or NO – 

This switch determine if the Fan is 

kept on during the Purge Mode, after the end of each heat or 
cool call.  

 

STAT RV – O or B – 

When using HP type thermostats this 

determines if the O or B terminal is wired to the W/OB terminal 
on each thermostat to determine if the call if for Heat (B) or 
Cool (O).  

  

TSTAT – HC-HP 

Switch determines if conventional Heat/Cool 

thermostats or Heat Pump thermostats are being used for ALL 
zones.    A  conventional  HC  stat  would  have  separate  W  and  Y 
output for heating and cooling calls.  A HP thermostat uses Y for 
both a heat and cool call and the O or B is used to determine 
whether  the call is for Cooling (O) or Heating (B). 

 

EM HEAT

 

– 

This  switch  sets  any  heat  call  to  call  for  the 

Emergency Heat.  The Red EM HEAT LED on the panel will light 
only when this switch is ON.  This is used when there is no Emer 
Heat switch on the thermostats.   

 

TEST – 

This switch accelerates the panel timings in order to 

provide a quick checkout of all of the functions without having 
to wait the full time for each sequence.   

 

 

One of the many features of the DIP switches is if at anytime the 
equipment  is  changed  from  single  stage  to  heat  pump  or  vice 
versa the thermostats do not need to be changed with the 
equipment change.  Changing the DIP switch settings is all that 
is needed.  

 

 
Leaving Air and Outdoor Air Sensor  

The Leaving Air Sensor, Model ZPS, is a remote sensor that is 
located in the supply air duct to sense the Leaving Air 
temperature of the HVAC Unit.  The ZPS is a high limit 
protection for the heating and a low limit protection for the 
cooling.  When zoning, the airflow through the HVAC Unit is 
critical.  The ZPS protects the equipment in low air flow 
situations as well as when by-pass air is being directed back into 
the return air duct.   
 
The heating limit is adjustable from 110

°

F to 170

°

F.  The cooling 

limit is fixed at 45

°

F.  When the ZPS senses heating above its set 

point, or cooling below its set point, the H32P will drop both all 
stages of heating or cooling.  The ZPS must sense a 10

°

F fall for 

heating or rise for cooling before re-activating the first stages of 
heating or cooling.  If two stage heating or cooling is being used 
the second stage timer will start again once the first stage is re-
activated.  

110

120

130

140

150

160

170

HIGH LIMIT

 

 
 
 

Содержание Uni-Zone H32P Series

Страница 1: ...H32P Uni Zone Model H32PP Installation and Operating Instructions TM ...

Страница 2: ... most convenient location and closest to power the HVAC unit controls and the zone dampers when typically located at or near the plenum The H32P panel case is made of sturdy ABS plastic and can be mounted to any flat surface It is recommended that the panel be mounted to a wall or return plenum and NOT on the furnace or plenum where it will be in contact with the excessive hot temperatures The pan...

Страница 3: ...32P is factory set for conventional heating and cooling operation The panel only needs to be configured when using with an electric furnace or heat pumps Most all of the panel configuration is done by setting the DIP switches in the top right of the panel Other functions come by wiring for specific applications Below is shown the most typical settings Review each function for you application SYSTE...

Страница 4: ...enever a call is made for either heating or cooling the changeover timer is activated in order to track the amount of time heating or cooling is on When an opposite call is made after a first call is existing the changeover timer calculates the amount of time the unit has already been supplying the first mode in order to determine how long it will hold off the opposite call If an opposite call is ...

Страница 5: ... R W2 E Y2 Y COMPRESSOR RELAY G FAN RELAY R 24V TRANSFORMER C HVAC EQUIPMENT TERMINALS HEAT PUMP EQUIPMENT W2 SECOND STAGE and EMERGENCY HEAT O REVERSING VALVE B REVERSING VALVE WIRING DIAGRAM 6 Two Speed Compressor Heat Pump Y O G W1 B R W2 E Y2 Y COMPRESSOR RELAY G FAN RELAY R 24V TRANSFORMER C HVAC EQUIPMENT TERMINALS W3 Third Stage Heat and EMERGENCY HEAT O REVERSING VALVE COOL B REVERSING VAL...

Страница 6: ... IN PURGE YES B STAT RV O HC TSTAT HP ON EM HEAT OFF ON TEST OFF ZONE 1 DAMPER ZONE 2 DAMPER ZONE 3 DAMPER ZONE 1 DAMPER ZONE 2 DAMPER ZONE 3 DAMPER C O B R Y G E E G Y R W OB C HEAT PUMP THERMOSTAT C O B R Y G E E G Y R W OB C HEAT PUMP THERMOSTAT C O B R Y G E E G Y R W OB C HEAT PUMP THERMOSTAT LAS LAS OAS OAS Leaving Air Sensor In Supply Air Duct Outdoor Air Sensor only used with Fossil Dual F...

Отзывы: