             Form 2263-110506                             MMP2 Installation and Operating Instructions                           ©2017 ZONEFIRST

®

 

 

 
 
 
 
INSTALLATION 

The  Mini-MasterZone

  Plug-In Damper  Zoning  System-2,  Model  MMP2, 

is a two (2) zone control panel for single stage heating only, cooling only or 
heating  and  cooling.      The  MMP2  can  control  any  single  stage  gas-oil-
electric furnace, hydro-air heating and air conditioning. The  MMP2 panel 
is  the  central  control  panel  where  all  zone  dampers,  zone  thermostats, 
HVAC Equipment and power transformer are wired.   
 
When installing the MMP2 panel it is important to pick a central location 
where it is most convenient to bring all the wires.  Most often this is near 
the  furnace  or  air  handler  and  closest  to  power,  the  HVAC  unit  controls 
and the zone dampers when typically located at or near the plenum. 
 
The  MMP2  case  and  cover  are  made  of  sturdy  ABS  plastic  and  can  be 
mounted  to  any  flat  surface.    It  is  recommended  that  the  panel  be 
mounted to  a  wall  or  return plenum  and NOT  on the  furnace  or  plenum 
where it will be in contact with the high heating temperatures.  The panel 
can be located in an attic space or in an enclosed cabinet of a rooftop unit, 
provided the panel enclosed and not in direct exposure to the elements.   
 
The  cover  easily  removes  from  the  case  by  pulling  firmly  and  separating 
the cover from the case exposing the circuit board.  There are 4 key-hole 
mounting points in each corner of the case.  The case has openings in the 
rear of  the case as well as  the side for all wiring.  Wiring can come from 
the back as well as the side in order to make a neat installation.   

 
 
OPERATION 

The  MMP2  controls  single  stage  heating  and  cooling  HVAC  Equipment.  
The  MMP2  is  compatible  with  any  standard  single  stage  thermostat  and 
setback thermostats as well.   The MMP2 has various features that make 
installation and c

heckout very simple for all of the board’s functionality.  

 

 
The  MMP2

’s  basic  function  is  zone  control.    On  a  call  for  heating  or 

cooling, the panel will accept the first call from any zone.  Upon accepting 
this call the MMP2 will keep open the damper(s) to the zone calling, close 
the  damper(s)  to  those  zones  not  calling,  activate  the  needed  HVAC 
controls  for  heating  or  cooling,  whichever  is being  called  and not  accept 
any calls for the opposite mode.  
  
Any calls for the opposite mode will be locked out until the initial mode is 
either  satisfied  or  a  period  of  time  has  elapsed  that  is  sufficient  for  the 
first  mode  to  satisfy,  a  maximum  of  20  minutes.    A  Patent  Pending 
sequence  determines  the  time  the  unit  has  been  running  or  needs  to 
continue  to  run  in  order  to  adequately  provide  conditioning  for  each 
mode.    If  a  particular  mode  has  already  been  calling  for  20  minutes  or 
longer and an opposite call comes in the MMP2 will immediately drop the 
mode, enter the purge mode in order to dissipate the conditioned air into 
the  zones  calling  before  switching  over  to  provide  the  new  conditioning 
call to its zones.   
 

 
 
PURGE TIME 

Once a call is satisfied the MMP2 drops the call for the heating or cooling 
unit controls, whichever was calling and hold the damper(s) to the zone(s) 
that  were  last  calling  during  the  Purge  Mode.    The  Purge  mode  is 
nominally 2 minutes and allows the excess conditioned air in the plenum 
to be distributed only to the zone(s) that were last calling.  This eliminates 
the problem of overshooting the temperature in the satisfied zones.    
 

Once all zone thermostats are satisfied for heating and cooling, the MMP3 
can  now  accept  Fan  calls  allowing  Continuous  Air  Circulation  (CAC)  in 

those zones where the thermostat’s Fan Switch is set to 

 

 
ON.    These  zone  dampers  will  be  OPEN  while  the  dampers  to  the  zones 
where the Fan Switch is set to AUTO will be CLOSED.   
 
When all zone thermostats are satisfied for both Heating and Cooling, and 
all Fan switches are set to AUTO position, the HVAC unit will be off and all 
zone dampers will return to a normally open position.  Once a zone calls 
for heating, cooling or fan, the dampers to the calling zones remain open 
and the dampers to the zones not calling will close.   

 
 
HVAC Equipment Set-Up 

The MMP2 is factory set for conventional fossil fuel (oil or gas) single stage 
heating and cooling.   
 
Jumpers  on  the  panel  are  for  NO  SENSOR  and  TEST.    The  NO  SENSOR 
jumper  must  be  placed  on  both  pins  when  the  sensor  (ZPS)  is  not  used.  
The TEST jumper (when placed on both pins) accelerates the panel timings 
in order to provide a quick checkout of the panel functions. During typical 
operating conditions this jumper 

should not

 be on both pins 

   

CHANGEOVER TIMER 

Whenever  a  call  is  made  for  either  heating  or  cooling,  the  changeover 
timer is activated in order to track the amount of time heating or cooling 
is  on.    When  an  opposite  call  is  made  after  a  first  call  is  existing  the 
changeover timer calculates the amount of time the unit has already been 
supplying the first mode in order to determine how long it will hold off the 
opposite  call.    If  an  opposite  call  is  made  shortly  after  the  first  call,  the 
opposite call may be held off for as much as 20 minutes.  If the first call or 
subsequent  calls for  the  first  call  mode  has had that  mode  operating  for 
up to 20 minutes already and an opposite call comes in after 20 minutes, 
the  changeover  timer  will  immediately  recognize  the  opposite  call, 
shutting  off  the  current  mode,  enter  the  purge  mode  and  automatically 
switch to the opposite mode.   
 
The longer a call has been running up to 20 minutes, the shorter the wait 
time  will  be  for  an  opposite  call.    If  a  call  is  over  20  minutes  and  an 
opposite  call  is  made  the  changeover  will  be  immediate  following  the 
purge  time.    This intelligent  changeover  timing  makes the  MMP2  unique 
to any other zoning system.   

 
 
CHECKOUT 

The  MMP2  has unique  features that  simplify  the  checkout  of  the  system 
and has LED readouts that constantly indicate the system operation.  Once 
24 Volt Power is applied to the panel the Green Power LED will illuminate.  
This will stay illuminated constantly when power is applied.   
 
The System LED will provide several different indications based upon color 
and if it is flashing.   
 

Heat ON             - RED 
Heat Over Limit  - RED Flashing 
Cool ON             - GREEN 
Cool Over Limit  - Green Flashing 
Fan ON              - AMBER 
Purge                 - AMBER Flashing 
 

Each zone has its own small Green indicator LED next to each zone relay.  
This light is lit whenever the zone damper is to be open, either on a call or 
when all zones are satisfied.    
 

 