background image

Form 2045-0803                                                        © Copyright Trolex Corporation & ZoneFirst                                                           

P a g e

 | 3 

6 Aspen Drive - Randolph, NJ 07869 | 1-877-FirstZone (347-7896)  

ZoneFirst.com | Shop Online at ZoneDampers.com | fb.com/ZoneFirst 

INSTALLATION 

The MasterZone

 Zoning System-4 is a four (4) zone control panel that 

controls up to four zones of heating and cooling.  The MZS4 panel is the 
central  control  panel  that  all  zone  dampers,  zone  thermostats,  HVAC 
Equipment,  power  transformer,  Leaving  Air    Sensor  and    ZoneAdder

 

panels are wired.   
 
When installing the MZS4 panel it is important to pick a central location 
where it is most convenient to bring all the wires.  Most often this is at 
the furnace or air handler.  It is often the most convenient location and 
closest to power, the HVAC unit controls and the zone dampers when 
typically located at or near the plenum.   
 
The MZS4 panel is made of sturdy ABS plastic and can be mounted to 
any flat surface.  It is recommended that the panel be mounted to a wall 
or return plenum and NOT on the furnace or plenum where it will be in 
contact with the hot temperatures..  The panel can be located in an attic 
space or in an enclosed cabinet of a rooftop unit, in order for the panel 
to be in direct exposure to the elements.   
 
The cover easily removes from the case by pulling firmly and separating 
the cover from the case exposing the circuit board.  There are 4 key-hole 
mounting  points  in  each  corner  of the case.    The  case  has  openings  in 
the rear of the case as well as the side for all wiring.  Wiring can come 
from the back as well as the side in order to make a neat installation.   

 

OPERATION 

The  MZS4  can  control  various  types  of  HVAC  Equipment  all  from  the 
same  panel.    The  MZS4  features  allow  the  use  of  single  stage 
thermostats to control up to three stage heating and two stage cooling 
and  simple  heat  pump  thermostats  to  control  heat  pumps.    The  MZS4 
has various features that make installation and checkout very simple for 
all of the board’s functionality.   
 
The  MZS4’s  basic  function  is  zone  control.    On  a  call  for  heating  or 
cooling,  the  panel  will  accept  the  first  call  from  any  zone.    Upon 
accepting  this  call  the  MZS4  will  open  the  damper(s)  to  the  zone(s) 
calling,  close  the  damper(s)  to  those  zones  not  calling,  activate  the 
needed HVAC controls for heating or cooling, whichever is being called 
and not accept any calls for the opposite mode.   
 
Any calls for the opposite mode will be locked out until the initial mode 
is either satisfied or a period of time has elapsed that is sufficient for the 
first  mode  to  satisfy,  a  maximum  of  20  minutes,  when  both  calls  occur 
simultaneously.  An exclusive sequence determines the time the unit has 
been running or needs to continue to run in order to adequately provide 
conditioning  for  each  mode.    If  a  particular  mode  has  already  been 
calling for 20 minutes or longer and an opposite call comes in the MZS4 
will  immediately  drop  the  mode,  enter  the  purge  mode  in  order  to 
dissipate the conditioned air into the zones calling before switching over 
to provide the new conditioning call to its zones.   
 
When using the MZS4 to control multi-stage heating and/or cooling, the 
extra stages are controlled based upon time after the first stage call from 
the  thermostat.    When  any  zone  calls  the  panel’s  built-in  timer  begins 
and after the set period of time elapses the MZS4 will also activate the 
W2 for Heating or Y2 for Cooling.  In heating, after the second stage is 
activated  the  same  timer  will  control  the  third  stage  of  heating.    The 
Stage Timer is adjustable from 5 to 23 minutes after the first stage call.  
Once the extra stages are on, these stages will continue to run until the 
first  stage  is  satisfied  or  the  Leaving  Air  Sensor

 

limit  setting  is  reached.  

(See Leaving Air section for further information.) 
 
Once  all  zone  thermostats  are  satisfied  for  heating  and  cooling,  the 
MZS4 will accept Fan calls allowing Continuous Air Circulation(CAC) in 
those  zones  where  the  thermostat’s  Fan  Switch  is  set  to  ON.    These 
zone dampers will be Open while the dampers to the zones where the 
Fan Switch is set to AUTO will be CLOSED.   
 
When  all  zone  thermostats  are  satisfied  for  both  Heating  and  Cooling, 
and all Fan switches are set to AUTO position, the HVAC unit will be off 
and  all  zone  dampers  will  return  to  a  normally  open  position.    Once  a 
zone calls  for  heating, cooling  or  fan,  the  dampers  to  the  calling  zones 
remain open and the dampers to the zones not calling will close.   

Set-Up for Various HVAC Equipment 

The MZS4 is factory set for conventional fossil fuel (oil or gas) single and 
up to three stage heating and two stage cooling.  The panel only needs 
to  be  configured  when  using  with  an  conventional  electric  furnace  or 
hydro-air system in order to bring the fan on with a call for heat, or when 
using with a heat pump equipment and thermostats.   
 
Most all of the panel configuration is done by setting the DIP switches in 
the lower center of the panel.  Below is show their setting and functions.   

 

1.

 

HP  EQP

  –  Heat  Pump  Equipment –  This  switch  changes  the 

output  of  the  HVAC  Equipment  terminals  from  conventional 
Heating  and  Cooling  to  a  traditional  Heat  Pump  Output.  
When  OFF,  a  heat  call  activates  the  W1  output  and  the 
second  stage  activates  W2.    When  ON  a  Heat  call  activates 
the  Y1  output  to bring  on  the  compressor  for  first  stage  and 
Y2 for the second stage, of both heating and cooling.  W3 is 
activated on a third stage call in either mode.  

2.

 

FAN HEAT 

– Activates the G output to turn the Fan on with a 

call  for  Heat.    This  is  used  for  Heat  Pumps,  Electric  Heat 
furnaces  and  Hydro-Air  Systems.    In  the  OFF  position  the 
MZS4 will not activate the Fan in heating unless there is a fan 
call from one of the zone thermostats.   

3.

 

O  TO  W 

–  Switch  Is  placed  to  ON  when  using  Heat  Pump 

thermostats  that  use  an  O  terminal  to  activate  the  reversing 
valve in COOLING.  The O on the thermostat is wired to W 
on  the  zone  terminal  in  order  to  determine  if  the  call  is  for 
heating or cooling.  All zone thermostats must operate and be 
wired the same way.   

4.

 

B TO W 

– Switch is used when using Heat Pump thermostats 

that  use  a  B  terminal  to  activate  the  reversing  valve  in 
HEATING.  The B terminal on the thermostat is wired to W on 
the  zone  terminal  in  order  to  determine  if  the  call  is  for 
heating or cooling.  All zone thermostats must operate and be 
wired the same way.  

NOTE:  Some OEMs use the B terminal 

as a transformer Common and not as the heating reversing 
valve.    These  thermostats  will  use  the  O  terminal  for  the 
reversing  valve  and  should  be  wired  accordingly  using  DIP 
Switch  #3.    The  B  terminal  will  then  be  wired  to  the  C 
terminal on the thermostat terminal block.   

5.

 

FAN  PRG  – 

This  switch  keeps  the  fan  running  during  the 

purge  time  in  order  to  dissipate  the  conditioned  air  into  the 
last  zone(s)  calling.    Placing  this  switch  to  ON,  prevents  the 
fan  from  turning  off  from  the  fan  control  in  the  HVAC  Unit 
during the purge mode and coming back on moments later if 
another  call  is  waiting.    In  OFF  the  fan  will  be  control  by 
HVAC Fan controls.  This is desirable in residential to prevent 
cold drafts after heating by having the switch OFF.  

 

6.

 

EMG HEAT – 

EMERGENCY HEAT – This switch can be used 

to  place  all  zones  into  the  Emergency  Heat  mode.    This 
switch  would  be  used  when  single  stage  thermostats  are 
used.   

NOTE:    There  is  no  indication  on  the  panel  to  show 

this switch is ON.  

 

7.

 

ZONE  STG  – 

STAGE  CONTROL  –  This  switch  is  used  to 

control  how  the  second  stage  of  heating  and  cooling  is 
determined.    In  the  OFF  position,  the  second  stage  is 
controlled by the timer.  In the ON position the second stage 
is  brought  based  on  the  number  of  zones  calling.    Greater 
than 50% of the zones calling will bring on the second stage, 
for both heating and cooling.  

 

8.

 

CTRL 3 – 

Future Use

 

 
One  of  the  many  features  of  the  DIP  switches  is  if  at  anytime  the 
equipment is changed from single stage to heat pump or vice versa the 
thermostats  do  not  need  to  be  changed  with  the  equipment  change.  
Changing the DIP switch settings is all that is needed.  

 

 
 
 

 1       2      3      4      5      6      7     8 

ON 
OFF 

Содержание MASTERZONE MZS4

Страница 1: ...MASTERZONE ZONING SYSTEM 4 Zones For use with the 24V Damper Motors Model MZS4 Installation and Operating Instructions Controlling Your Comfort Room By Room ...

Страница 2: ...ES Zone Terminals for Zone Damper Motors and Zone Thermostats 24VAC Transformer Terminals Re Settable Fuse Zone Calling Indicators Mode DIP Switches HVAC Equipment Terminals Leaving Air Sensor Terminals ZONE ADDER RJ11 Connection Adjustable Heating Limit Mounting Keyholes Two at Top also Adjustable Second Stage Timer Power Indicator LED Boot Button System Mode Indicator LED Purge Override Button N...

Страница 3: ...n CAC in those zones where the thermostat s Fan Switch is set to ON These zone dampers will be Open while the dampers to the zones where the Fan Switch is set to AUTO will be CLOSED When all zone thermostats are satisfied for both Heating and Cooling and all Fan switches are set to AUTO position the HVAC unit will be off and all zone dampers will return to a normally open position Once a zone call...

Страница 4: ...ly the fan may be running during this time and the damper s to the last zone s calling will remain open to purge the conditioned air only into those zones that were calling for the conditioning DIP Switch 5 can be set ON to keep the Fan running during the Purge mode in order to prevent the fan cycling off and back on between modes In the instance where the Fan staying may create a draft and the fr...

Страница 5: ...MENT AIR TO AIR HEAT PUMP CONNE CTIONS HEAT PUMP CONTROLS W2 W1 Y1 Y2 O G E B R W3 Compressor Relay Reversing Valve 24V Transformer Second Stage Heat Relay Emergency Heat Relay Fan Relay EQUIPMENT AIR TO AIR HEAT PUMP CONNE CTIONS HEAT PUMP CONTROLS W2 W1 Y1 Y2 O G E B R W3 TROUBLESHOOTING The MZS4 is a very simple control to troubleshoot especially with the LED indicators The only other device ne...

Страница 6: ...GLESTAGETHERMOSTAT E G R W O B Y C CLOSE OPEN COM ZONE CONNECTIONS C Y W R G SINGLESTAGETHERMOSTAT E G R W O B Y C CLOSE OPEN COM ZONE CONNECTIONS C Y W R G SINGLESTAGETHERMOSTAT E G R W O B Y C CLOSE OPEN COM ZONE CONNECTIONS C Y W R G SINGLESTAGETHERMOSTAT E G R W O B Y C CLOSE OPEN COM ZONE CONNECTIONS C Y W R G SINGLESTAGETHERMOSTAT E G R W O B Y C CLOSE OPEN COM ZONE CONNECTIONS C Y W R G SIN...

Отзывы: