BPE Installation Instructions #BPE20651508 

© 2015 ZONEFIRST 

 

 

Control Panel Features 

 
 

The Bypass Eliminator™ (Model BPE) Control is an interface 
between  a  ZONEFIRST  Zone  Control  Panel  and  its  zone 
dampers.    The  BPE  is  used  to  eliminate  the  need  for  a 
traditional separate by-pass duct and damper directed back 
into  the  return  duct.    The  BPE  can  ONLY

ONLY

ONLY

ONLY  be  used  with 

ZONEFIRST’S Plug-In Zone Dampers and control panels.   
 
The BPE uses an air sensor in the duct system on the supply 
side  and  before  all  zone  dampers  so  it  can  monitor  the 
systems static pressure, whenever the blower is running.  The 
zone  dampers  are  now  wired  directly  into  the  BPE  and  not 
the  zone  control  panel.    The  BPE  has  4  zone  inputs  where 
the damper outputs of the zone control panel will plug-in on 
the  BPE.  The  zone  control  panel  controls  the  zone  dampers 
through the BPE.    
 
The  BPE  will,  on  an  increase  in  static  pressure  in  the  duct 
system,  modulate  the  closed  dampers  to  gradually  open  to 
relieve the air pressure back below the high set-point.  When 
this occurs the zone dampers will stop.      
INSTALLATION

INSTALLATION

INSTALLATION

INSTALLATION    
The BPE can be mounted against flush surface and should be 
located  within  10’  of  where  the  pressure  sensor  tube  is 

placed  in  the  duct.    Ideally  if  mounted  next  to  the  zone 
control  panel  this  will  minimize  the  length  of  wires  for  the 
interconnection of the panels for the zone dampers.   
 
It  is  recommended  that  the  panel  be  mounted  to  a  wall  or 
return  plenum  and  NOT  on  the  furnace  or  plenum  where  it 
will  be  in  contact  with  the  high  heating  temperatures.    The 
panel  can  be  located  in  an  attic  space  or  in  an  enclosed 
cabinet of a rooftop unit, provided the panel is enclosed and 
not in direct exposure to the elements.   
 
The cover easily removes from the case by pulling firmly and 
separating  the  cover  from  the  case  exposing  the  circuit 
board.  There are 4 key-hole mounting points in each corner 
of the case.  The case has openings in the rear of the case 
as well as the side for all wiring.  Wiring can come from the 
back as well as the side in order to make a neat installation.   
CONTENTS

CONTENTS

CONTENTS

CONTENTS    
The  BPE  includes  10  feet  of  pressure  tubing  (which  can  be 
cut down to size), as well as a duct probe, and four 7 foot 
telephone  cables  to  interface  the  BPE  with  the  zone 
controller. 
    

LCD Menu Screen 

24VAC Transformer 
Terminals 

Menu 
Configuration 
Buttons 

Output to Zone Dampers 

Zone Damper input  
Connections from 
zone board 

Pressure Input 