INSTALLATION INSTRUCTIONS 

 

PEDESTAL PUMPS 

DEWATERING AND SUMP 

 

81, 82, 84 SERIES

  

PREINSTALLATION CHECKLIST — ALL INSTALLATIONS 

Notice to Installer:  Instructions must remain with installation. 

PUMP PERFORMANCE/GALLONS PER MINUTE DEWATERING AND SUMP 

 

   

Vertical lift of pump                   81 Series                           82 Series                          84 Series

     Feet        Meters     Gallons     Liters      Gallons      Liters     Gallons      Liters

       

5               1.5                50             189               50             189              59              223

        10              3.0                36             136               41             155              51              193

        15              4.6                10              38                28             106              38              144

        20              6.1                --                --                  4               15               17               64

        Shut-off Head                 16 ft. (4.9 m)                 21 ft. (6.4 m)                 24 ft. (7.3 m)

 

© Copyright 2003 Zoeller Co. All rights reserved.

Product information presented 

here reflects conditions at time 

of  publication. Consult fac-

tory regarding discrepancies or 

inconsistencies.

MAIL TO:

  P.O. BOX 16347 • Louisville, KY  40256-0347

SHIP TO:

  3649 Cane Run Road  • Louisville, KY  40211-1961

(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624

visit our web site:

http://www.zoeller.com

SEE BELOW FOR

LIST OF CAUTIONS

SEE BELOW FOR

LIST OF WARNINGS

1.   Inspect your pump.

 Occasionally, products are damaged during shipment.  If the unit is damaged, contact your dealer before using.

2.   Carefully read the literature

 provided to familiarize yourself with specific details regarding installation and use. These materials should be 

retained for future reference.

Tested to UL Standard UL778

& Certified to CSA

Standard C22.2 No. 108

1.

 

Make sure there is a properly grounded receptacle available. 

All pumps are 

furnished with provisions for proper grounding to help protect you against the 

possibility of electrical shock. 

(SEE WARNING BELOW)

2.

 Make certain that the receptacle is within the reach of the pump’s power supply 

cord. 

DO NOT USE AN EXTENSION CORD.

 Extension cords that are too long or 

too light do not deliver sufficient voltage to the pump motor. But more important, 

they could present a safety hazard if the insulation were to become damaged or 

the connection ends were to fall into the sump.

3.

 

Make sure the pump electrical supply circuit is

 

equipped with fuses or circuit 

breakers of proper capacity.

 A separate branch circuit is recommended, sized 

according to the National Electrical Code for the current shown on the pump motor 

identification label.

4.

 Installation and checking of electrical circuits and hardware should only be performed 

by a qualified licensed electrician.

5.

 A proper cover should be placed over the pit whenever a column pump is installed to 

help protect against injury and to prevent debris from falling into the pit.

6. FOR YOUR PROTECTION ALWAYS DISCONNECT PUMP FROM ITS POWER 

SOURCE BEFORE HANDLING. 

Single phase pumps are supplied with a 3-prong 

grounded plug to help protect you against the possibility of electrical shock. 

DO 

NOT UNDER ANY CIRCUMSTANCES REMOVE THE GROUND PIN. 

The 3-

prong plug must be inserted into a mating 3-prong grounded receptacle. If the 

installation does not have such a receptacle, it must be changed to the proper 

type, wired and grounded in accordance with the National Electrical Code and 

all applicable local codes and ordinances.

7.                 DO NOT USE FOR PUMPING FLAMMABLE LIQUIDS.

8.

 According to the state of California (Prop 65), this product contains chemicals known to 

the state of California to cause cancer and birth defects or other reproductive harm.

1.

 Check to be sure your power source is capable of handling the voltage 

requirements of the motor, as indicated on the pump motor identification 

label.

2.

 

Note: This unit is designed for indoor applications where the motor is 

mounted above the pit cover and protected from water, water spray, 

and high humidity.

3. 

Maximum continuous operating temperature for standard model pumps must 

not exceed 130°F (54°C).

REFER TO WARRANTY ON PAGE 2.