INSTALLATION INSTRUCTIONS 

MODEL 519 Condensate Pump

NOTICE TO INSTALLER:  Instructions must remain with installation.

P/N 155408

© Copyright 2018 Zoeller

®

 Co. All rights reserved.

1.    To help reduce the risk of electrical shock, a properly grounded 

receptacle or control box of grounding type must be installed and 

protected by a ground fault circuit interrupter (GFCI) in accordance 

with the National Electrical Code and applicable local codes.  If 

pump is wired direct, a GFCI must be installed in the control box. 

(SEE WARNING BELOW)

2.  Make certain that the ground fault interrupter protected receptacle 

or control box is within reach of the pump’s power supply cord. 

DO NOT USE AN EXTENSION CORD. Extension cords that are 

too long or too light do not deliver sufficient voltage to the pump 

motor. But more important, they could present a safety hazard if 

the insulation were to become damaged or the connection end 

were to fall into a damp or wet area. 

 3.   Make sure the pump's electrical supply circuit is equipped 

with fuses or circuit breakers of proper capacity. A separate 

branch circuit, sized according to the National Electrical Code 

for the current shown on the pump name plate is recommended.

1.    Inspect all materials. Occasionally, products are damaged during shipment. If the unit is damaged, contact your dealer before using.

2.    Carefully read all the literature provided to familiarize yourself with specific details regarding installation and use before attempting the installation. 

These materials should be retained for future reference. 

                  

1.    Check to be sure your power source is adequate to handle the 

amperage requirements of the motor as indicated on the pump 

or unit I.D. tag. 

2.    All plumbing (discharge and drain lines) must be installed to meet 

local codes.   

3.    This pump has been evaluated for use with water only.                      

4.    TESTING FOR GROUND. As a safety measure, each electrical 

outlet should be checked for ground using an Underwriters 

Laboratory Listed circuit analyzer which will indicate if the power, 

neutral and ground wires are correctly connected to your outlet. 

If they are not, call a qualified licensed electrician.   

5.  Installation and checking of electrical circuits and hardware should 

only be performed by a qualified licensed electrician.

6.    FOR YOUR PROTECTION ALWAYS DISCONNECT PUMP FROM 

ITS POWER SOURCE BEFORE HANDLING.

7.  Prop65 Warning for California residents: Cancer and Reproductive 

Harm- www.P65Warnings.ca.gov.

CAUTION

SEE BELOW FOR

LIST OF CAUTIONS

REFER TO WARRANTY ON PAGE 2.

NOTE: Pumps with the “UL” mark and pumps with the “US” mark are 

tested to UL Standard UL778. CSA Certified pumps are certified to CSA 

Standard C22.2 No. 108.

SEE BELOW FOR

LIST OF WARNINGS

Product information presented 

here reflects conditions at time 

of  publication. Consult factory 

regarding discrepancies or 

inconsistencies.

MAIL TO:  P.O. BOX 16347 • Louisville, KY  40256-0347

SHIP TO:  3649 Cane Run Road  • Louisville, KY  40211-1961

TEL: (502) 778-2731 • 1 (800) 928-PUMP • FAX: (502) 774-3624

Visit our web site:

zoellerpumps.com

Register your 

Zoeller Pump Company 

Product on our website:

http://reg.zoellerpumps.com/

Содержание 519

Страница 1: ...llationandusebeforeattemptingtheinstallation These materials should be retained for future reference 1 Check to be sure your power source is adequate to handle the amperage requirements of the motor as indicated on the pump or unit I D tag 2 All plumbing discharge and drain lines must be installed to meet local codes 3 This pump has been evaluated for use with water only 4 TESTING FOR GROUND As a ...

Страница 2: ...arbon derivatives oil gasoline solvents etc wash towels or feminine sanitary products etc or other abrasive or corrosive substances Limited Warranty This warranty is in lieu of all other warranties expressed or implied andwedonotauthorizeanyrepresentativeorother person to assume for us any other liability in connection with our products Contact Zoeller Pump Company 3649 Cane Run Road Louisville Ke...

Страница 3: ... ground fault protected circuit DO NOT ever cut splice or damage power cord DO NOT carry or lift pump by its power cord DO NOT use an extension cord with this condensate pump Ten Helpful Hints or Easy Installation Do s and Do Nots or Installing Unit 5 DO NOT use a discharge pipe smaller than the pump discharge size 6 DO test pump immediately after installation to be sure that the system is working...

Страница 4: ...downward slope to allow for gravity flow Note Local codes may require the use of a condensate neutralizer when using this pump Note Make sure the drain lines from the A C condenser are supported above the reservoir and no weight from the drain line is directed to the bottom of the reservoir SK3177 SK1765 SK3178 STEP 1 Mounting Location STEP 2 Installation of Condensate Drain Lines CONDENSING GAS F...

Страница 5: ...Kink or Pinch off blocking flow Figure 3 1 SK3179 STEP 3 Installation of Discharge Line STEP 4 Installation of Safety Switch GFCI Outlet Pipe Supports To Main Drain Floor Joists 15 FT Max RECOMMENDED NOT INCLUDED HOSE CLAMP 3 8 IDTubing Inverted U Note Condensate Drain Lines not Shown Refer to Step 2 for Installation of Drain Lines POWER CORD SAFETY SWITCH LEADS INLETS 4 MOUNTING BRACKET 2 DISCHAR...

Страница 6: ...houldactivate breakingthethermostatcircuittotheappliance 4 Plug the pump in and allow the pump to empty the tank As the water level decreases the appliance will reset STEP 5 Testing of Pump Operation Maintenance Guidelines Cleaning of Reservoir 1 Remove entire pump from wall if mounted 2 Disassemble reservoir from the deck by inserting a screwdriver in either side of the deck 3 Clean reservoir as ...

Страница 7: ...elines section for cleaning instructions Refer to Maintenance section for cleaning instructions Measure from bottom of pump to highest point Rework discharge if height is greater that 18 Refer to STEP 3 for guidelines Check discharge line for blockage remove debris Refer to Maintenance section for cleaning instructions Contact Factory Contact Factory Refer to Maintenance section for cleaning instr...

Страница 8: ...8 Zoeller Co All rights reserved MAILTO P O BOX 16347 Louisville KY 40256 0347 SHIPTO 3649 Cane Run Road Louisville KY 40211 1961 502 778 2731 1 800 928 PUMP FAX 502 774 3624 Visit our web site zoellerpumps com NOTES ...

Отзывы: