H0439100.C - EN - 2015-01
9
5. Troubleshooti ng
5.1 Displays
Display
Designati on
Cause
Soluti on
Reset
Protecti on of heat
exchanger in cold
mode
Temperature of ST4
sensor too low
Wait for the surrounding
temperature to become
warmer
Automati c
High temperature
defect for the
evaporator in
«cooling» mode
Temperature probe ST3
above 60°C or evaporator
scaled up
Clean the evaporator,
if the defect persists,
contact an approved
technician
Automati c if
temperature probe ST3
is below 45°C
Phase order defect
(only on three-
phased models)
• Wiring incorrect on the
supply terminal board
of the device,
• Modifi cati on of phase
order by electrical
supplier,
• Temporary failure of
one or several phases
• Reverse the phases on
the supply terminal
board (without power
to the device)
• Contact your electricity
provider to fi nd out
if modifi cati ons have
been made to your
equipment.
Switch the power
supply off or press
Refrigerant circuit
low pressure defect
Low pressure circuit
pressure defect (if the
defect remains aft er
reset)
Contact an approved
technician
Automati c reset (for
less than 4 defects per
hour) or press
Refrigerant circuit
high pressure defect
• Water and air mixture
passing in the appliance,
• Unsati sfactory water
fl ow,
• Blocked fl ow controller
• Clogged or blocked heat
exchanger
• Check the pool
hydraulic circuit
• Increase the fl ow-rate
using the by-pass, check
that the pool fi lter is
not clogged)
• Check the fl ow-rate
controller
• Clean the exchanger
• If the defect persists,
contact an approved
technician
Automati c reset (for
less than 4 defects per
hour) or press
Compressor
discharge
temperature defect
Compressor discharge
temperature too high
Contact an approved
technician
Press
for 3 seconds
Control sensor
defect (ST1)
Sensor out-of-order or
disconnected (connector
J2 red on plate A1)
Replace or reconnect the
sensor
Switch the power
supply off or press
Water fl ow-rate
sensor defect (ST4)
Sensor out-of-order or
disconnected (connector
J8 white on plate A1)
Replace or reconnect the
sensor
Switch the power
supply off or automati c
reset if the defect
disappears
Defrost sensor
defect (ST3)
Sensor out-of-order or
disconnected (terminals
1-2 of connector J3 white
on plate A2)
Replace or reconnect the
sensor
Switch the power
supply off or press
This symbol means that your appliance must not be disposed of as household waste. It will be subject to selecti ve
waste sorti ng with a view to its reuse, recycling or sale. If it contains substances that are potenti ally harmful to the
environment, they will be eliminated or neutralised.
Ask your reseller for informati on about recycling.
4.2 Available accessories
Name
PAC NET
Remote
control
Wintering cover
Technical room
kit
Condensate pan
Representati on
4.3 Recycling
Содержание Z300 Series
Страница 13: ...Notes ...
Страница 25: ...Notes ...
Страница 37: ...Notes ...
Страница 49: ...Notes ...
Страница 61: ...Notes ...
Страница 73: ...Notes ...
Страница 85: ...Notes ...
Страница 87: ...H0439100 C ML 2015 01 2 Z300 T5 ...
Страница 88: ...H0439100 C ML 2015 01 3 Z300 MD5 ...
Страница 89: ...H0439100 C ML 2015 01 4 Z300 MD8 ...
Страница 90: ...H0439100 C ML 2015 01 5 Z300 TD5 TD8 ...
Страница 95: ......