ZMIO310 Vertical Bus Expansion Module User Manual V1.0
Mark
Interface
Number
Description
RUN
The light
indicates states.
1
Run state: green, it lights when runs normally
ERR
1
Error state: red, it lights when runs incorrectly
Local expansion front level interface
1
Connect to coupler modules or expansion
submodules, plug in and pull out when in hot
are unsupported.
Local expansion behind level interface
1
Connect to expansion submodules, plug in
and pull out when in hot are unsupported.
Signal indicator
IO signal indicator
1
Correspond to each signal indicator.
User terminal
1
16 digital outputs / power terminal
4.2.2.
Performance & Specification
Item
Specification
ZMIO310-16DO
ZMIO310-16DOP
Power voltage
24VDC
The number of outputs
16
The type of output
Digital output
The method of output
Leakage (NPN, it is low electric
level when there is output)
Source (PNP, it is high electric
level when there is output)
Output overcurrent protection
Max is 300mA, and the max tripping current is 600mA.
The max leakage current when
OFF
25
μ
A
25
μ
A
Respond time when OFF
12
μs
12
μs
Respond time when ON
80μs
60μs
Internal power
0.3W
Power
1.3W
Isolation
Coupler isolation
Frequency (output)
<8kHz
Action showing (output)
When the output is ON, output indication led will be ON.
Service
Firmware upgrade