Moreover, if a door is not closed within a specified period after it is opened, the door control panel will
also raise the alarm. It is recommended to select two-core wires with a gauge over 0.22 mm
2
. A door
sensor can be omitted if it is unnecessary to monitor the open/closed status of a door, raise the alarm
when the door is not closed for a long time, monitor if there is unauthorized access, and use the interlock
function.
2.
Exit switch
An exit switch is a switch installed indoor to open a door. When it is switched on, the door will be opened.
An exit button is fixed at the height of about 1.4m above the ground. Ensure it is located in the right
position without slant, and its connection is correct and secure. (Cut off the exposed end of any unused
wire and wrap it with insulating tape.) Make sure to avoid electromagnetic interference (such as light
switches and computers). It is recommended to use two-core wires with a gauge over 0.3mm
2
as the
connection wire between an exit switch and the Control panel.
3.
Auxiliary input
TheInBio160 Pro provides one auxiliary input interface; the InBio260 Pro provides two and theInBio460
Pro provides four, which may connect to infrared body detectors, smoke detectors, gas detectors, window
magnetic alarms, wireless exit switches, etc. Auxiliary inputs are set through the relevant access control
software. Please see the
ZKAccess 4.0 user manual
for further details.
Figure 3-3 Connections between InBio460 Pro and Door Sensors, Exit Switches, and Auxiliary Input Devices