P/N 10-4211-501-ZX01-01 • ISS 26JAN15 

After installation, ensure that the detector communicates with 
the control panel. Always test detectors after installation. 

To remove a locked detector: 

1.  Insert a small screwdriver into the locking tab slot  

(Figure 3). 

2.  Press and rotate the detector anticlockwise. 

Setting the address 

The detector includes a seven-segment DIP switch (SW1) for 
assigning detector addresses. Each switch segment has a 
decimal value as shown in Figure 4. The address is the sum of 
all the switch segments in the ON position. The full DIP switch 
address range of 1 to 127 is shown on page 4. 

For example, to select a detector address of 007, set SW1-1, 
SW1-2, and SW1-3 to the ON position and the remaining 
switch segments to the OFF position. 

Locking base option 

The detector is compatible with a range of bases (see 
“Specifications”) and is easily installed by a simple twist and 
lock action.  

Note: 

To prevent unauthorised removal of a detector from its 

base, an automatic locking tab is incorporated into all detector 
mouldings. If the tab is removed, detectors can only be 
released from their bases by use of a screwdriver, as shown in 
Figure 3. This locking option is applied at the system 
commissioning stage. 

Maintenance and testing 

Basic maintenance consists of a yearly inspection. Do not 
modify internal wiring or circuitry. 

Automatic self-test 

Sensor sensitivity, calibration and self-testing are carried out 
automatically by the fire panel. Removal or replacement of an 
incorrect sensing detector will be identified by the system and 
shown as a fault. 

 

Specifications 

 

Operating voltage 

19.5 to 20.5 V pulsed,  
max. 4 V line loss 

Current 
 

Standby 

 

Alarm 

 
600 µA 
700 µA 

Coverage 
 

Smoke element 

 

Thermal element 

 

100 m

 

50 m

 

IP Rating 

IP32 

Polarity sensitive 

Yes 

Compatible bases 

Z-AUXD-2P 
ZP7-IB-P 
ZP7-RB1-P 
ZP7-SB1-P 
ZP7-SB1B, Black 
ZP755B-2P 
ZP755BV-4P 
ZP755BV-5P 

Compatible accessories 

Z-RL3 Remote LED unit 
Z-RL4 Remote LED unit 

Operating environment 
 

Temperature 

 

Storage temperature

 

Relative humidity 

 
–10 to +85°C 
–20 to +70°C 
20 to 95% noncondensing 

Dimensions (Ø x H) 

106 × 58 mm 

Weight 

105 g 

 

Regulatory information 

 

This section includes both regulatory information and a 
summary on the declared performance according to the 
Construction Products Regulation 305/2011. For detailed 
information refer to the product Declaration of Performance.

 

 

Certification 

 

Certification body 

0370 

Declaration of 
Performance number 

360-4211-1099  

Year of first CE 
marking 

14 

Product identification 

ZX832-3 

Intended use 

See DoP point 9  

Essential 
characteristics  

See DoP point 9  

Manufacturer 

United Technologies Safety System Co., Ltd.  
80, Changjiang East Road, QETDZ,  
066004 Qinhuangdao, HEBEI, China 

Authorized EU manufacturing representative: 
UTC Fire & Security B.V. Kelvinstraat 7, 6003 
DH Weert, Netherlands  

 

2012/19 /EU (WEEE directive): Products 
marked with this symbol cannot be disposed 
of as unsorted municipal waste in the 
European Union. For proper recycling, return 
this product to your local supplier upon the 
purchase of equivalent new equipment, or 
dispose of it at designated collection points. 
For more information see: 
www.recyclethis.info. 

 

Отзывы: