P/N 10-4211-501-ZX01-01 • ISS 26JAN15
After installation, ensure that the detector communicates with
the control panel. Always test detectors after installation.
To remove a locked detector:
1. Insert a small screwdriver into the locking tab slot
(Figure 3).
2. Press and rotate the detector anticlockwise.
Setting the address
The detector includes a seven-segment DIP switch (SW1) for
assigning detector addresses. Each switch segment has a
decimal value as shown in Figure 4. The address is the sum of
all the switch segments in the ON position. The full DIP switch
address range of 1 to 127 is shown on page 4.
For example, to select a detector address of 007, set SW1-1,
SW1-2, and SW1-3 to the ON position and the remaining
switch segments to the OFF position.
Locking base option
The detector is compatible with a range of bases (see
“Specifications”) and is easily installed by a simple twist and
lock action.
Note:
To prevent unauthorised removal of a detector from its
base, an automatic locking tab is incorporated into all detector
mouldings. If the tab is removed, detectors can only be
released from their bases by use of a screwdriver, as shown in
Figure 3. This locking option is applied at the system
commissioning stage.
Maintenance and testing
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Automatic self-test
Sensor sensitivity, calibration and self-testing are carried out
automatically by the fire panel. Removal or replacement of an
incorrect sensing detector will be identified by the system and
shown as a fault.
Specifications
Operating voltage
19.5 to 20.5 V pulsed,
max. 4 V line loss
Current
Standby
Alarm
600 µA
700 µA
Coverage
Smoke element
Thermal element
100 m
2
50 m
2
IP Rating
IP32
Polarity sensitive
Yes
Compatible bases
Z-AUXD-2P
ZP7-IB-P
ZP7-RB1-P
ZP7-SB1-P
ZP7-SB1B, Black
ZP755B-2P
ZP755BV-4P
ZP755BV-5P
Compatible accessories
Z-RL3 Remote LED unit
Z-RL4 Remote LED unit
Operating environment
Temperature
Storage temperature
Relative humidity
–10 to +85°C
–20 to +70°C
20 to 95% noncondensing
Dimensions (Ø x H)
106 × 58 mm
Weight
105 g
Regulatory information
This section includes both regulatory information and a
summary on the declared performance according to the
Construction Products Regulation 305/2011. For detailed
information refer to the product Declaration of Performance.
Certification
Certification body
0370
Declaration of
Performance number
360-4211-1099
Year of first CE
marking
14
Product identification
ZX832-3
Intended use
See DoP point 9
Essential
characteristics
See DoP point 9
Manufacturer
United Technologies Safety System Co., Ltd.
80, Changjiang East Road, QETDZ,
066004 Qinhuangdao, HEBEI, China
Authorized EU manufacturing representative:
UTC Fire & Security B.V. Kelvinstraat 7, 6003
DH Weert, Netherlands
2012/19 /EU (WEEE directive): Products
marked with this symbol cannot be disposed
of as unsorted municipal waste in the
European Union. For proper recycling, return
this product to your local supplier upon the
purchase of equivalent new equipment, or
dispose of it at designated collection points.
For more information see:
www.recyclethis.info.