SE
R
IA
L N
o
PRESS HERE TO
LOG ON
3.5 - 4.5V DC
0.2 - 300mA
1W Max
SE
R
IA
L N
o
PRESS HERE TO
LOG ON
3.5 - 4.5V DC
0.2 - 300mA
1W Max
Wireless RIM Base
EN54-25: 2008
Technical Data refer to Installation guide
Part No: ZR401-RL
0359-CPR-00424
Ziton Wireless Remote Indicator Installation Guide
General
The Ziton wireless remote indicator and ancillary
equipment are available under the following part
numbers:
PART NO
VARIANT TYPE
ZR4-RL
Ziton wireless remote indicator
c/w wireless base
ZR401-RL
Ziton wireless remote indicator
base (no remote indicator)
ZX4-RL
Ziton wireless remote indicator
(no wireless base)
The address of the unit is set when programming the
device to the system (see programming manual for
details). The installation must conform to BS5839: Part 1
(or applicable local codes).
Installation of Ziton wireless remote indicator
Ensure that all detectors are sited in accordance with the
survey and design details.
First disengage the remote indicator from the wireless
module by turning it counter clockwise. This exposes the
user features in the wireless module, see Figure 2.
Disengage the mounting plate by pressing down the
locking pin, see Figure 2, and turn the wireless module
counter clockwise whilst pressing it against the
mounting plate.
This dis-assembles the mounting plate from the wireless
module and remote indicator sections, see Figure 1. The
mounting plate is now free to be fixed to the wall or
ceiling.
To guarantee correct operation, connect the power
jumper across the PIN header on the wireless module
located under the remote indicator, see Figure 2.
©2018 EMS Ltd. All rights reserved
1 / 4
4 / 4
TSD170 Iss 4 17/10/2018 AJM
©2018 EMS Ltd. All rights reserved
Figure 1
Ident
Locking mechanism
Power jumper
Figure 2
Notes
TSD170 Iss 4 17/10/2018 AJM
Mounting Plate
Wireless Module
Remote Indicator
Fix Mounting Plate
Fix the mounting plate using suitable fixings and
fasteners. All four mounting holes must be used, see
Figure 3 for highlighted mounting holes.
When wall mounting, to ensure the text
description of the head is shown correctly, the
mounting plate should be installed in the orientation
shown in Figure 3.
It is important that fastener heads are flush or sub-flush
with the internal surface of the ceiling mount to avoid
the risk of damaging the battery PCB.
!