P/N 501-1787ZE-1-09 • REV 09 • ISS 16APR14 

Figure 3: Address switch setting 

 

Mode and tone settings 

The sounder includes a seven-segment DIP switch (SW2) 
used to select operating mode, device mode, and tone. Refer 
to Figure 4. 

Figure 4: Mode of operation switch settings 

1

2

3

4

5

 

1. 

Power selection jumpers 

2. 

SW2 configuration switch 

3. 

Tone setting 

4. 

Device mode 

5. 

Stand-alone mode 

Setting the operating mode 

The device operates as a dedicated (stand-alone) sounder with 
its own unique loop address when SW2-7 is set to ON. 

 

 

To configure operation as a stand-alone sounder: 

1.  Set SW2-7 to ON. 

2.  Navigate to the following menu to tag the sounders as 

SAB: 

ZP3 Panel Menu/Setup/Sounders/SAB/Add SAB

  

The Planner can also be used. 

3.  To map an alert-to-evac function, make the first input type 

a fast flash input.  

The sounder will sound the alert tone in response to a fast 
flash input or an evac tone when the input configured as 
steady is triggered, overriding the alert tone. 

Setting the device mode 

SW2-6 selects whether the loop sounder operates in ZP755 
mode or in ZP754 emulation mode as described in Table 1. 

Table 1: SW2-6 mode selection switch 

Mode 

SW2-6 

Output Signal 

Requirement 

ZP755 

OFF 

User-selectable two-tone 
operation and full 
monitoring  

ZP3 software 
v1.18 or later 

ZP754 
emulation  

ON 

Two fixed tones 

ZP5 panels or 
ZP3 panels with 
legacy software 

Setting the tone  

Two different tones can be programmed to operate from the 
panel. In ZP755WV-2R mode these tones are selected using 
SW2-1, SW2-2, and SW2-3. Refer to Table 2. 

Note: 

In the ZP panel I/O mapping menu, outputs are 

programmed as "steady" or "flashing." The link to the table 
below is as follows: 

• 

Tone A = Panel setting "fast flash/slow flash.”  

• 

Tone B = Panel setting "steady.”  

 

 

 

 

 

 

 

 

 

 

 

 

 