2 / 4
P/N 10-5202-501-ZV01-12 • ISS 05OCT21
Setting the address
The sounder includes a seven-segment DIP switch (SW1) for
assigning device addresses. Each switch segment has a
decimal value as shown in Figure 3. The address is the sum of
all the switch segments in the ON position. The switch is used
to set the device address in binary code. The switch may be
set to represent any address from 1 to 127.
For example, to select a device address of 007, set SW1-1,
SW1-2, and SW1-3 to the ON position and the remaining
switch segments to the OFF position.
Figure 3: Address switch setting
Mode, tone, and volume settings
The sounder includes a seven-segment DIP switch (SW2) to
select the operating mode, tone, and volume. See Figure 4.
Figure 4: Mode of Operation switch settings
1. Power selection jumpers
2. SW2 configuration switch
3. Tone
4. Addressing mode
5
Visual indicator operating
mode
6. Volume
Setting the
addressing mode
Configure the base sounder to operate with or without a
detector at the same address as shown in Table 2.
Table 2: Setting address mode
Switch
Setting
SW2-4
OFF
The sounder is stand-alone with a unique
loop address not used by another detector.
SW2-4
ON
The sounder shares the address with a
detector to expand the number of devices
supported by the loop.
Configure the base sounder to enable or disable the visual
indicator as shown in Table 3.
Table 3: Setting Visual Indicator operating mode
Switch
Setting
SW2-5
ON
Enable the
visual indicator.
SW2-5
OFF
Disable the
visual indicator.
Not recommended with
Silent tone.
Setting the volume
Use SW2-6 and SW2-7 to set the volume. Level 1 is the lowest
volume setting, and level 4 is the highest as shown in Table 4.
Refer also to the measured anechoic sound levels in Figure 7.
Table 4: Volume settings
00 – Level 1
10 – Level 2
01 – Level 3
11 – Level 4
Average dBA measurement
3 dBA less than
level 2.
3 dBA less
than level 3.
3 dBA less
than level 4.
Certified tones
[1].
[1] UK-continuous, UK intermittent, UK two-tone are EN 54-3
compliant.
Setting the tone
The control panel can operate the sounder in two different pre-
programmed tones, by selecting SW2-1, SW2-2, and SW2-3.
Refer to Table 5 Tone settings.
Note:
Two additional tones are available, the Class change
and the Visual indicator only tone. However, these tones may
not be available for legacy control panels. Please refer to the
configuration options of your control panel to confirm tone
availability.
Table 5
: Tone settings
Device mode
SW2 switch setting -1-2-3
Primary warning
Secondary evacuation
Attention (nonfire)
ZP755
0
UK intermittent
UK continuous
Class change
ZP755
1
UK continuous
UK two-tone
Class change
ZP755
2
UK two-tone
UK intermittent
Class change
ZP755
3
Australian whoop
Australian alert
Class change
ZP755
4
Swedish tone
Dutch slow whoop
Class change
ZP755
5
ISO8201
French two-tone
Class change
ZP755
6
German
Visual indicator only
Class change
ZP754
7
UK intermittent
UK continuous
Class change
1
2
3
6
4
5