background image

2 / 4 

 

P/N 10-5202-501-ZV01-12 • ISS 05OCT21 

Setting the address 

The sounder includes a seven-segment DIP switch (SW1) for 

assigning device addresses. Each switch segment has a 

decimal value as shown in Figure 3. The address is the sum of 

all the switch segments in the ON position. The switch is used 

to set the device address in binary code. The switch may be 

set to represent any address from 1 to 127. 
For example, to select a device address of 007, set SW1-1, 

SW1-2, and SW1-3 to the ON position and the remaining 

switch segments to the OFF position. 

Figure 3: Address switch setting 

 

Mode, tone, and volume settings 

The sounder includes a seven-segment DIP switch (SW2) to 

select the operating mode, tone, and volume. See Figure 4. 

Figure 4: Mode of Operation switch settings 

 

1.  Power selection jumpers 

2.  SW2 configuration switch 

3.  Tone 

4.  Addressing mode 

Visual indicator operating 

mode 

6.  Volume 

Setting the 

addressing mode 

Configure the base sounder to operate with or without a 

detector at the same address as shown in Table 2. 

Table 2: Setting address mode 
Switch 

Setting   

SW2-4 

OFF 

The sounder is stand-alone with a unique 

loop address not used by another detector. 

SW2-4 

ON 

The sounder shares the address with a 

detector to expand the number of devices 

supported by the loop. 

Configure the base sounder to enable or disable the visual 

indicator as shown in Table 3. 

Table 3: Setting Visual Indicator operating mode 
Switch 

Setting   

 

SW2-5 

ON 

Enable the 

visual indicator. 

 

SW2-5 

OFF 

Disable the 

visual indicator. 

Not recommended with 

Silent tone. 

Setting the volume 

Use SW2-6 and SW2-7 to set the volume. Level 1 is the lowest 

volume setting, and level 4 is the highest as shown in Table 4. 

Refer also to the measured anechoic sound levels in Figure 7. 

Table 4: Volume settings 
00 – Level 1 

10 – Level 2 

01 – Level 3 

11 – Level 4 

 

 

 

 

Average dBA measurement 

3 dBA less than 

level 2. 

3 dBA less 

than level 3. 

3 dBA less 

than level 4. 

Certified tones 

[1]. 

[1] UK-continuous, UK intermittent, UK two-tone are EN 54-3 

compliant. 

Setting the tone 

The control panel can operate the sounder in two different pre-

programmed tones, by selecting SW2-1, SW2-2, and SW2-3. 

Refer to Table 5 Tone settings. 

Note: 

Two additional tones are available, the Class change 

and the Visual indicator only tone. However, these tones may 

not be available for legacy control panels. Please refer to the 

configuration options of your control panel to confirm tone 

availability. 

 

Table 5

: Tone settings 

Device mode 

 

SW2 switch setting -1-2-3 

Primary warning 

Secondary evacuation 

Attention (nonfire)

 

ZP755 

 

UK intermittent 

UK continuous 

Class change 

ZP755

 

 

UK continuous

 

UK two-tone

 

Class change

 

ZP755

 

 

UK two-tone

 

UK intermittent

 

Class change

 

ZP755

 

 

Australian whoop

 

Australian alert

 

Class change

 

ZP755

 

 

Swedish tone

 

Dutch slow whoop

 

Class change

 

ZP755

 

 

ISO8201

 

French two-tone

 

Class change

 

ZP755

 

 

German

 

Visual indicator only

 

Class change

 

ZP754 

 

UK intermittent 

UK continuous 

Class change 

 

1

2

3

6

4

5

Отзывы: