background image

Installation Sheet  

No.: 1453 iss 01 

ZP3-RDUB1 Remote Display Unit 

Installation sheet 

 

501-1453ZE-1-01 

ZP3-RDUB1 Remote Display Unit 

Page 1 

14/12/2005 

 

Description 

The  ZP3-RDUB1  Remote  Display  Unit  (Repeater 
Panel)  mimics  the  status  of  a  host  ZP3  Panel  at  a 
remote  location.    Bi-directional  communication 
between  them  is  via  the  ZP3  Serial  Control  Bus 
(SCB), which makes use of a RS485 link. 

The RDU Panel has the RDU Display and RDU Zone 
Boards  mounted  to  its  door.    The  door  has  cut-outs 
prepared  for  access  to  push-button  switches,  LED’s 
and  the  LCD.  The  door  is  closed  by  a  Camlock.  The 
Controls  Key  can  be  software  enabled  in  the  host 
panel  to  control  access  to  the  Accept,  Reset,  Sound 
Alarms and Silence buttons. 

Wiring  to  the  RDU  Panel  is  done  through  the  
knock-outs situated at the back of the panel. 

Specification 

Compatibility: 

ZP3 Panels 

Software: 

SW72301.XXX, SW72201.XXX 

Data Interface: 

ZP3 Serial Control Bus (RS485) 

24V Power Supply: 

 

Voltage 

24Vdc (-20% +25%) 

Current (quiescent) 

150mA 

Current (max) 

300mA 

Current (LCD 

100mA 

backlighting off) 

Display Type: 

Euro 4 x 40 LED 

Primary LED 

Common Fire, Common 

indications: 

Fault, Common Disabled, 

 

Other, Silence Alarms, Sound 

 

Alarms 

Secondary LED Indicators  

26 LEDs 

No. of Zone indications 

50 

Audible Alarms: 

On-board buzzer to 
acknowledge key presses 
and signal alarms. 

Pushbutton Switches: 

14 

Keyswitches: 

Controls On/Off 

Jumper Links: 

 

Controls Enable (L1) 

Enables Accept, Reset, 
Sound Alarms and Silence 
Alarms 

Reset Comms 

Resets the communications 

Controller (L11) 

microcontroller 

Reset Main Controller (L12)  Resets the display 

microcontroller 

Buzzer Mute (L16) 

Kills the buzzer (only with 
commissioning terminals 
shorted) 

Termination (L2) 

Terminates the RS485 line 
with 120

 

Fail-safes (L5, L6) 

Used together to apply a fail-
safe bias to the RS485 line 

Terminals: 

 

Earth (TB4.1) 

Connect to building earth 

0V & +24V (TB4.2&3) 

24V DC supply 

Comms (TB3) 

RS485 connection to the 
Serial Control Bus 

Crls Off (TB2.1&2) 

Not used 

Commis (TB2.3&TB5.1) 

Link to place RDU in 
commissioning mode (buzzer 
mute) 

Reserved (TB5.2&3) 

Connection for the controls 
on/off keyswitch 

Dimensions: 

358mm (W) x 220mm (H) x 
52mm (D) 

Weight:  

2.7 kg 

EN60529 Rating: 

IP30 

Temperature Range: 

-5 to 45ºC 

Отзывы: