ZP2 Series Compact Repeater Installation Manual
13
Commissioning
After the compact repeater is installed and configured, the panel must be
commissioned.
Check the following:
• That the fire system is designed in accordance with all required regulations
and standards
• That the maximum alarm current in your installation does not exceed the
maximum current specifications of the power supply
• That all equipment is correctly installed and tested and that all cabling
complies with the recommendations outlined in “Recommended cables” on
page 9
• That all software functions are correctly programmed
• That all inputs and outputs operate correctly
• That any input/output logic (rules and actions) configuration is correct
• That the fire system is functioning correctly in standby and is not reporting
any alarms or faults
• That under the alarm conditions (with all applicable devices activated), the
current consumption does not exceed the power supply specifications