997-532-000-1, Issue 1
March 2006
25
EN54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
7
Configuration
Access Level 3 allows input, output and control functions
to be configured.
The following sections describe how to configure the
panel. Each procedure requires the panel status to be
at access Level 3. The state of the configurable options
is indicated by the panel LEDs.
The table at left shows the functions of each pushbutton
at access Level 1/ 2 and Level 3.
The Configuration menus are as follows:
1 Miscellaneous: Panel Options; System
2 Zones: either 1- 2, 1- 4 or 1- 8
3 Output circuits: 1- 4*
4 Digital Inputs: 1 and/ or 2
5 Delays: first stage; second stage.
*
Each output can be configured as a monitored or volt-
free relay output. Output circuits 3 and 4 can be provided
using the optional 2-way Relay PCB (kit ZIRCON/EN/
FFR).
Manual Zones
The odd-numbered zones are configured as manual,
i.e. MCP-only, zones. Manual zones can be changed so
they can form part of a day-time delay strategy.
7.1
Entering Access Level 3
To enter access Level 3: hold down the
pushbutton
and press the following pushbuttons in the order given -
,
and
.
Rapid flashing of the FIRE LED
confirms that the panel is at access Level 3
. You can
now access the configuration options in any order.
The Level 3 function of each pushbutton is indicated
using an icon within brackets immediately above each
pushbutton.
Press the following pushbuttons to select menu options:
- Panel/ System Options
- Zone Input/ EOL Type
- Output Type/ Delay
- Digital Inputs
- Delays.
Press
to cycle through the sub-menu. Press
at
anytime to return to the Top Level menu.
See the configuration map on the back cover of this
manual for a quick reference guide.
ISO 7240-2 : 14.5.3e), f)
Installers must make a
record of the configuration
details of the panel and store
the information at access
level 3.
ISO 7240
!
ISO 7240
!
A copy of the configuration map (see the
back page) marked up and dated would
make a suitable record. Any change of
configuration will require a new
configuration record.