background image

8.

  Place the element / holder assembly into the furnace.

9.

  Replace the braided contact straps if they show signs of wear. Otherwise, reinstall the used strap.

10.

  Pre-form new contact straps to fit the terminals by bending them over an old terminal or some 

other 6mm solid round mandrel.

11.

  Take care placing the spring clamps onto the contact straps. Keep the ends of adjacent spring 

clamps as far away from each other as possible so they do not short out against each other. Do not 

torque the element terminals when replacing the clamps.

12.

  Replace the top cover.

8. TROUBLESHOOTING 

1.  The controllers do not turn on when the power switch is turned on.

  The power cord is not plugged in.  

• 

 The fuse has blown.

•  The controller has failed and needs to be replaced.

2.  The programmable controller or over temperature controller do not indicate temperature.

•  If either controller is flashing oooo then the thermocouple to that controller is broken and 

must be either repaired or replaced.

  Check the control thermocouple and terminal block connections for a loose connection.

  Check the control thermocouple lead wire at the back of the controller for a loose connection.

3.  The furnace does not heat and the HEAT ON indicator (see appendix A #5) does not illuminate.

• 

 Check that the Heat switch is in the on position which is position l (see appenfix A #4).

•  Check that the Over Temperature Controller has been reset by seeing the red OUT LED light 

is off.

• 

 Unplug from the power source. Check the main power fuse inside the controller cabinet by using 

an Allen key to remove the side panel. Locate the power fuse on the back wall adjacent to the side 

panel and remove with a fuse puller.  Measure the fuse with a volt meter for continuity or high 

resistance. If the fuse is good the meter will beep for continuity or show a low resistance. 

4.  The furnace does not heat and the HEAT ON indicator is illuminated.

  Check that the furnce temperature (PV) displayed in green on the Over-Temperature Controller is 

not reading higher than the number displayed in orange (SV) (see appendix A #32 and #33). If the 

PV exceeds the SV, one of the following is possible:

-The overtemperature thermocouple is reading falsely hot. Replace the thermocouple.
-The overtemperature SV is set too low and may need to be reprogrammed.
-The furnace is overheated, wait for it to cool.

  Check that the overtemp controller is reset. If unsure as to whether or not it is reset, try to reset it 

again. The OUT light above the <RST button should be off (see appendix A #35).

9

Содержание Hot Spot 110

Страница 1: ...Hot Spot 110 User Guide Zircar Zirconia Inc www zircarzirconia com R 110M 01 Rev00...

Страница 2: ...Temperature Controller Configuration D REX P48 Temperature Controller Patterns Programs E CL100L Over Temperature Controller Configuration F SCR G REX P48 96 Series Programmable Temperature Controlle...

Страница 3: ...eference the chart below Model Voltage Amperage Hot Spot 110 110 120 20 Hot Spot 110 220 240 10 Hot Spot 110L 110 120 20 Hot Spot 110L 220 240 10 2 Disconnect all power from the furnace before opening...

Страница 4: ...gh temperature for a prolonged time and then cooled down may have internal stresses which can cause the protective silica glaze to splinter into small fragments There have been instances where heating...

Страница 5: ...e furnace chamber Typical contaminates are Previously processed material remnants Glaze which has fallen from the heating elements 5 An appropriate firing setter should always be used to protect the H...

Страница 6: ...ning the handle and lifting outwards and upwards until it catches on the latch see appendix A 7 Remove the packing material from the heating chamber Be careful not to touch the heating elements IMPORT...

Страница 7: ...ed position 5 Switch the green power switch to the ON position see appendix A 3 The light will turn green the fan will come on and the controllers will start up 6 Push the PTN1 PTN2 button on the prog...

Страница 8: ...revised If you MUST reduce the OT limit it can be reduced as follows 1 Press the SET button The rightmost digit will be highlighted in the lower orange display see appendix A 36 2 Press the v or butt...

Страница 9: ...er step 8 above will cause the furnace to power off at the end of that step Step 1 of the pattern will start at the actual temperature of the furnace when the pattern is run Example If the end point a...

Страница 10: ...bration and should be replaced For video instructions on how to replace the thermocouple go to www zircarzirconia com technical documents procedure replacing hotspot thermocouple Heating Elements Even...

Страница 11: ...tion 3 The furnace does not heat and the HEAT ON indicator see appendix A 5 does not illuminate Check that the Heat switch is in the on position which is position l see appenfix A 4 Check that the Ove...

Страница 12: ...nd braid connections were all good the meter should show low ohms which indi cates a dead short 5 The over temperature controller alarms during a firing Check the over temperature controller set point...

Страница 13: ...NY 10921 0827 www zircarzirconia com Phone 845 651 3040 Fax 845 651 0074 email sales zircarzirconia com Technical Information Sales Manager David C Hoskins Phone 845 651 3040 ext 137 Fax 845 651 0074...

Отзывы: