Discharge arrangement          

General guidance is provide by the diagram on page 19, extracted from the G3 Building 
Regulation Guidance. This guidance is available as a free of charge download of the G3 
Approved Document from www.planningportal.gov.uk.  
The discharge from both the Temperature relief and expansion relief valves can be joined 
together via a 15mm end feed Tee.
It is important that any discharge water does not collect in this pipe-work and can run freely to 
the tundish. The tundish should be mounted in a vertical and visible position located in the same 

space as the unvented hot water storage system and be fitted as close as possible and within 

600mm of the safety device e.g. the temperature relief valve. The discharge pipe-work from the 
tundish must be routed in accordance with Part G3 of the Building Regulations.
The discharge pipes and tundish should be installed in a visible location away from any electrical 
devices, should terminate in a safe place where there is no risk to persons in the vicinity of the 
discharge, be of metal and:

• 

Be at least one pipe size larger than the nominal outlet size of the safety device unless its 
total equivalent hydraulic resistance exceeds that of a straight pipe 9m long i.e. discharge 
pipes between 9m and 18m equivalent resistance length should be at least two sizes 
larger than the nominal outlet size of the safety device, between 18 and 27m  
at least 3 sizes larger, and so on. Bends must be taken into account in calculating the 

flow resistance. 

 

An alternative approach for sizing discharge pipes would be to follow BS6700 

Specification for design installation, testing and maintenance of services supplying water 

for domestic use within buildings and their curtilages.

• 

Have a vertical section of pipe at least 300mm long, below the tundish before any elbows 
or bends in the pipework.

• 

Be installed with a continuous fall.

•  It is preferable for the discharge to be visible at both the tundish and the final point of 

discharge but where this is not possible or practically difficult there should be clear 

visibility at one or other of these locations. 

Examples of acceptable discharge arrangements are:

•  Ideally below the fixed grating and above the water seal in a trapped gulley.
• 

Downward discharges at a low level; i.e. up to 100mm above external surfaces such as 
car parks, hard standings, grassed areas etc. are acceptable providing that a wire cage or 
similar guard is positioned to prevent contact whilst maintaining visibility.

• 

Discharges at a high level; e.g. in to metal hopper and metal down pipe with the end of 
the discharge pipe clearly visible or onto a roof capable of withstanding high temperature 
discharges of water and 3m from any plastic guttering systems that would collect such 
discharges.

Содержание AquaFlo II AF3090

Страница 1: ...ns carefully before commencing installation Please leave these instructions with the end user after installation Zip Heaters UK Ltd 14 Bertie Ward Way Dereham Norfolk NR19 1TE Telephone 0845 6024533 F...

Страница 2: ...Inside Back cover Inside Front cover...

Страница 3: ...mmissioning 22 Annual servicing 23 Warranty 24 Please read these instructions carefully before commencing installation of the AquaFlo unvented Water Heater Please leave these instructions with the end...

Страница 4: ...litre units Twin Coil and Solar Direct units are available in 5 sizes from 150 300 litres To help ensure compliance with the relevant Water and Building Regulations all AquaFlo units are supplied com...

Страница 5: ...ified The appliance must not be used for any purpose other than that for which it was designed When the appliance has been in use for some time the fittings may be very hot This appliance must not be...

Страница 6: ...bserve these instructions Technical data specification Maximum water supply pressure to pressure reducing valve 1 0 MPa 10 bar Note If supply is above 1 0 MPa 10 bar a pressure control valve must be u...

Страница 7: ...uctions Page 5 of 24 V 2 01 October 2012 Connection Points AquaFlo Indirect and Solar Compatible Immersion Cold Inlet Primary Coil T P Valve Stat Pocket Sec Return Primary Coil 38 35 25 40 66 15 Immer...

Страница 8: ...F3300 Nominal Capacity Litres 90 120 150 180 210 250 300 Diameter mm 545 545 545 545 545 545 545 Height mm A 727 915 1102 1290 1478 1728 2041 T P Valve mm B 515 703 890 1078 1266 1516 1829 Sec Return...

Страница 9: ...90 120 150 180 210 250 300 Diameter mm 545 545 545 545 545 545 545 Height mm A 727 915 1102 1290 1478 1728 2041 T P valve mm B 515 703 890 1078 1266 1516 1829 Sec return mm C 1159 1409 1609 Immersion...

Страница 10: ...8 1728 2041 Solar High Limit Thermostat Pocket mm B 890 1078 1266 1516 1829 Solar Auxillary Pocket mm C 890 1078 1266 1516 1829 T P Valve mm D 890 1078 1266 1516 1829 Secondary Return mm E 1159 1409 1...

Страница 11: ...545 Height mm A 1102 1290 1478 1728 2041 Solar High Limit Thermostat Pocket mm B 890 1078 1266 1516 1829 Solar Auxillary Pocket mm C 890 1078 1266 1516 1829 T P Valve mm D 890 1078 1266 1516 1829 Sec...

Страница 12: ...4 0 133 183 33 1102 150 AF3150 1 53 1 1 82 0 164 0 163 218 38 1290 180 AF3180 1 80 1 1 96 0 203 0 194 251 41 1478 210 AF3210 2 15 1 1 117 0 248 0 236 296 46 1728 250 AF3250 2 28 1 1 145 0 323 0 288 35...

Страница 13: ...g 23 30 38 42 45 51 60 Weight Full kg 111 148 186 220 253 299 357 Vol Within 10o C of Set Temperature Litres 74 105 132 160 188 232 285 Heat up 14 2 20 0 22 0 26 2 31 2 33 0 41 0 Re heat minutes Follo...

Страница 14: ...45 51 60 Weight Full kg 187 222 255 300 359 186 220 253 299 358 Volume within 10 C of Set Temperature Litres 132 160 188 232 285 132 160 188 232 285 Heat up minutes 1 x 3kW Immersion 54 1 82 7 97 9 11...

Страница 15: ...ion Heater Dual Stat SA20014 Solar High Limit Stat Not Shown 7 SA20011 2 Port Valve SA20013 Non Self Resseting Thermostat High Limit Not Shown SA20010 Separate Expansion Vessel Bracket Not Shown Parts...

Страница 16: ...um of 0 15 MPa 1 5 bar at 20 l m flow should be available Where mains inlet pressures are likely to exceed 1 2 MPa 12 bar then an additional upstream pressure reducing device should be fitted A minimu...

Страница 17: ...not be used for any other purpose and no valve should be fitted between the expansion relief valve and the storage cylinder Cold mains pipework Run the cold main through the building to the place whe...

Страница 18: ...o the primary flow pipework leading to the coil flow inlet The direction of flow arrow should be towards the primary flow connection On twin coil cylinders an extra thermostat boss is provided Seconda...

Страница 19: ...the AquaFlo single coil model with the Dual Control thermostat inserted into the middle stat pocket The wiring requirements are as depicted in this guide Lower coil Solar Installation In a solar power...

Страница 20: ...charge pipes between 9m and 18m equivalent resistance length should be at least two sizes larger than the nominal outlet size of the safety device between 18 and 27m at least 3 sizes larger and so on...

Страница 21: ...eration should be given to the installation of an electronically operated device to warn when discharge takes place Note The discharge will consist of scalding water and steam Asphalt roofing felt and...

Страница 22: ...TG ON DHW ON DHW OFF SL L N E E E 3 3 3 4 4 5 5 6 6 7 7 8 8 9 9 3 E L N 2 10 10 2 1 BI O G Y ROOM STAT WIRING CENTRE PROGRAMMER BOILER 2 PORT HEATING CUTOUT COMBINED dUOSTAT 2 PORT DHW PUMP Wiring Dia...

Страница 23: ...E L N 2 9 8 7 6 5 4 3 3 2 2 1 1 L L SL L N E N N N E E E 1 1 2 3 G Y HTG ON DHW ON DHW OFF ROOM STAT PROGRAMMER BOILER WIRING cENTRE 3 PORT MID POSITION CUTOUT COMBINED dUOSTAT 2 PORT DHW PUMP Wiring...

Страница 24: ...given to reducing this to 55 60 C In many healthcare applications the guidance on Legionella control and safe water delivery temperatures will require storing the water at 60 65 C distributing at 50 5...

Страница 25: ...water to drain away adequately If not check for blockages etc and clear WARNING THE WATER DISCHARGED MAY BE VERY HOT 2 Ensure that any immersion heaters that are fitted are working correctly and that...

Страница 26: ...at invoices for servicing may be requested to prove that the unit has been serviced annually All the components fitted to or supplied with the AquaFlo carry a 2 year warranty EXCLUSIONS The warranty d...

Отзывы: