Command & Parameter Details
Control Setup Data Items
These commands can be read to retrieve details on various moving variables within the controller.
The number typed into the box selects which data Item is to be read. Example, a value of 3 will
return the variable for the Speed Demand.
Note
–
Control Setup Data Items are different to Drive Setup Data Items.
Data Item Number
Details
0
State
–
what state the module is in (ie, stopped, running, waiting for
command etc..)
1
Fault Code
2
Fault Data
3
Speed Demand
–
Set from PID
4
Enable Input
–
debounced and after “Invert Settings” are applied
5
Direction Input
–
debounced and after “Invert Settings” are applied
6
Analogue Value
–
Filtered and follows the Analogue Scaler Values.
7
Pot Value - Filtered and follows the Analogue Scaler Values.
8
Speed Demand Slewed
–
Speed Demand with applied
Acceleration/Deceleration
9
Motor Speed in Hz
10
Supply Voltage in Vx10
11
Controller Temperature in DegC
Fault Codes & Fault Data
Fault Code
Cause
Fault Data Reading
0
No Fault
NA
1
Max Motor Current
101 = 10.1A last Reading
2
Max Power
301 = 301W last reading
3
Min Supply Voltage
49 = 4.9V
4
Max Supply Voltage
251 = 25.1V
5
Controller Temperature
101 = 101 degC
6
Motor Failed Start
5 = five failed attempts to start motor
7
Motor Stalled
100 = 100ms between seeing valid
Commutation Point
Invert Settings
Invert Settings Value Description
0
Both Enable and direction inputs are NOT inverted
1
Only Enable input is Inverted
2
Only Direction input is Inverted
3
Both the Enable and the Direction Inputs are inverted