ZIEHL UFR1001E Скачать руководство пользователя страница 7

 

UFR1001E 

12420-0751-00

  

Page

 

7 / 8 

 www.ziehl.de 

 

Menu

point 

Parameter / Unit 

Default settings 

Users data 

Low voltage 

Medium voltage 

3AC+N 

230V

 

3AC 

400V

 

3AC+N 

57,7V

 

3AC 

100V

 

3AC+N 

230V 

3AC 

400V 

Pr1 

*

 

Pr2 

Pr3 

Pr4 

Pr5

 

Pr6

 

 

F_  

  

F_  

  

 Alarm on/off 

 

  on 

  on 

  on    on    on    on  

 

  

F_  

  

 Underfrequency

 

Hz 

47.50 

47.50 

47.50  47.50  47.50  47.50 

 

  

H_  

  

 Hysteresis       

 

Hz 

 1.00 

 1.00 

 1.00   1.00   1.00   1.00 

 

  

dal  

 ON-delay    

 

 0.10 

 0.10 

 0.10   0.10   0.10   0.10 

 

  

dof 

  

 OFF-delay    

 

  60 

  60 

  60    60    60    60 

 

F__ 

  

F__ 

  

 Alarm on/off 

 

 - 

 - 

 off   off   off   off 

 

  

F__ 

  

 Underfrequency

 

Hz 

 - 

 - 

47.50  47.50  47.50  47.50 

 

  

H__ 

  

 Hysteresis       

 

Hz 

 - 

 - 

 1.00   1.00   1.00   1.00 

 

  

dal  

 ON-delay    

 

 - 

 - 

 0.10   0.10   0.10   0.10 

 

  

dof 

  

 OFF-delay    

 

 - 

 - 

  60    60    60    60 

 

vsr 

  

vsr 

  

 Alarm on/off

 

 

 off 

 off 

 off   off   off   off 

 

  

vsr 

  

 Vector shift

 

°

 

 10.0 

 10.0 

 10.0   10.0   10.0   10.0 

 

  

dof 

  

 OFF-delay    

 

   3      3 

   3     3     3     3 

 

  

dEon

  

 Suppression time          

   2 

   2 

   3     3     3     3 

 

  

vsr 

  

 Number of phases

 

 

 3ph 

 3ph 

 3ph   3ph   3ph   3ph 

 

rEL 

  

trEL

  

 Switching time 

Y1,Y2          

s

 

  5.0 

  5.0 

 off   off   off   off 

 

ddi 

  

ddi 

  

 Display delay

 

 s

 

  0.5 

  0.5 

  0.5    0.5    0.5    0.5 

 

  

dit 

  

 Display duration 

SCn 

  3.5 

  3.5 

  3.5    3.5    3.5    3.5 

 

Si 

  

U   

  

 Voltage 

 

V

 

 230 

 400 

 57.7   100   230   400 

 

  

F   

  

 Frequency

 

Hz

 

50.00 

50.00 

50.00  50.00  50.00  50.00 

 

  

vsr 

  

 Vector shift

 

°

 

  0.0 

  0.0 

  0.0    0.0    0.0    0.0 

 

CodE

 

  

pin 

  

 Pin code

     

 

 

 504 

 504 

 504   504 

504

 

504

 

 

Info 

  

fnr 

  

 Firmware version

     

  

 0-00   0-00   0-00   0-00   0-00   0-00 

 

  

snr 

  

 Serial number

     

 

 

xxxxx 

xxxxx 

xxxxx  xxxxx  xxxxx  xxxxx 

 

  

h   

  

 Operating hours

     

 h 

xxxxx 

xxxxx 

xxxxx  xxxxx  xxxxx  xxxxx 

 

  

err 

  

 Error counter

     

 

 

xxx 

xxx 

xxx 

xxx 

xxx 

xxx 

 

  

Pr  

  

 Program

     

 

 

   1 

   2 

   3     4     5

 

   6

 

 

 

* factory preset 

 

Display of the program

8

Info

8

 

 

8

Pr  

8

 

or when switching on 

Display of the firmware version

8

Info

8

 

 

8

fnr 

 

Protective functions, default settings according to VDE-AR-N 4105 section 6.5.2 

Voltage increase protection  

U>>  

 

8

U,  

8

 

1.15 Un    100 ms        

 

Voltage increase protection  

U>  

8

UM  

8

  

1.1 Un    100 ms        

Voltage decrease protection   

U< 

8

U_  

8

  

0.8 Un    100 ms        

Frequency increase protection  

f>  

8

f,  

8

  

51.5 Hz    100 ms        

Frequency decrease protection 

 

f<  

8

f_  

8

  

47.5 Hz    100 ms        

Содержание UFR1001E

Страница 1: ...ceeded Flashing 8AL 8 OFF delay 8dof 8 active 4 LEDs Relay status yellow OFF Relays de energized ON Relays energized 5 Digital display 4 digit red Depending on program display of current voltage frequ...

Страница 2: ...imulation enabled Description of the connections A1 and A2 Rated control supply voltage Us see Technical Data any polarity 11 12 14 21 22 24 Relay K1 and K2 E1 E2 Enable input needed only for vector s...

Страница 3: ...ent clearance to other devices or heat sources If cooling is inhibited e g through close proximity to devices with increased surface temperature or interference with the cooling air current the permis...

Страница 4: ...button 5x Display 8Pr 1 8 Set the program with the buttons Press button 1x Display 8 no 8 Press button 1x Display 8 yes 8 Press button Device resets and starts with the newly selected program Hint Wh...

Страница 5: ...s Up Down simultaneously sets the values to the smallest one Code Reset Press button Set 2 s while applying control supply voltage Pin 504 Error reports Err4 Tolerance Master Slave Err5 internal regul...

Страница 6: ...Overvoltage V 253 438 253 438 253 438 HM Hysteresis V 3 0 3 0 3 0 3 0 3 0 3 0 dal ON delay s 0 10 0 10 0 10 0 10 0 10 0 10 dof OFF delay s 60 60 60 60 60 60 U_ u_ Alarm on off on on On On on on u_ Un...

Страница 7: ...h rEL trEL Switching time Y1 Y2 s 5 0 5 0 off off off off ddi ddi Display delay s 0 5 0 5 0 5 0 5 0 5 0 5 dit Display duration SCn s 3 5 3 5 3 5 3 5 3 5 3 5 Si U Voltage V 230 400 57 7 100 230 400 F F...

Страница 8: ...r88 appears in the display Hysteresis error overlapping of the release points Upper threshold value must be higher than the lower threshold value check the threshold values 8Err98 appears in the displ...

Отзывы: