UFR1001
12290-0702-05
Page
7 / 25
www.ziehl.de
Caution! If the operating current execution is programmed for all relays, a failure of
the control voltage or the device will not be detected.
When using as a monitoring device, the operator must ensure that this error
is detected through periodic performance tests.
We recommend programming and correspondingly evaluating at least one relay
in closed-circuit (idle) current execution.
Comply with the maximum permissible temperature when installing in a switch cabinet. Ensure
sufficient clearance to other devices or heat sources. If cooling is inhibited, e.g., through close
proximity to devices with increased surface temperature or interference with the cooling-air current,
the permissible ambient temperature is decreased.
Caution!
Before you apply mains voltage to the device, make sure that the permissible control
voltage
Us
on the side rating plate matches the mains voltage connected to the device!
7
Mounting
The device can be mounted:
•
Distribution board or switch cabinet on 35 mm rails according to EN 60715
8
Detailed description
8.1 Description of the connections
Connection
Function
A1 and A2
Control voltage Us, see 12. Technical data
11, 12, 14
Relay K1, menu item
8
AL1U.
8
,
8
aL1F.
8
21, 22, 24
Relay K2, menu item
8
AL2U.
8
,
8
aL2F.
8
E1
– E2 (Pr 4-5)
Enable input
Floating opener
Contact closed = UFR 1001 disabled, no evaluation of voltage,
frequency and vector surge
Open = UFR 1001 enabled, voltage, frequency, and vector surge will
be evaluated
Y1
– Y2 (Pr 1-3)
external reset
Floating closing contact
Function same as pressing the Set/Reset key for >2 s
nc
Not used
N
Neutral conductor
L1
Phase L1
L2
Phase L2
L3
Phase L3