8.9 Overview of commissioning
Must
Can
Overview
X
8.10 Selection of program number
X
8.11 Switch on device
X
8.12 Configure the sensors
X
8.13 Configure the alarms
X
8.14 Configure the relay test on K1
X
8.15 Configure the Modbus RS 485 interface (option)
X
8.16 Sensor simulation
X
8.17 Code block
8.18 Tips on operating
8.19 Possible indications in display
8.10 Selection of program number
Set the program number as described in Point [6. Programs].
8.11 Switch on device
Switch on supply voltage,
All LEDs and displays are illuminated
Displays the set measurand
Displays the set program number
After ca. 2s, the TR440 is operable
8.12 Configure the sensors
Starting from the display mode:
Return into the display mode by pressing Set key ≥ 2s
If no entry is made for 30 s, the device also returns to the display mode.
Press Down key
Display
8
S 1.
8
Press the Set key
Set sensor type using the Up / Down key
8
nc.
8
=> not connect
ed
, no sensor connected
8
3-L.
8
=> 3-wire Pt 100 sensor
8
00.0.
8
…
8
99.9.
8
=> 2-wire Pt 100 sensor, specification of the entire
line resistance from the sensor outgoing and return line
Press the Set key
Select the next sensor with the Down key (with Up key to the previous sensor or to exit the
menu modus in sensor
8
S 1.
8
)
Configure the next sensor
After Sensor 4 (in program 1 after Sensor 3), change to the next menu item with the Down
key (alarms configuration)