13  Technical data 

 

 

Control voltage Us: 

DC/AC 24 – 240 V 0/50/60 Hz 

Tolerance 

DC 20,4 - 297 V 

AC 20 - 264 V 

Power consumption 

< 2 W 

< 6 VA 

 

Relay outputs K1...K9 

9 x 1 switching contact 

Switching voltage 

max 300 V AC; 300 V DC 

Normally open (NO) inrush current 

AC 15 A 4s 10% ED 

Minimum values Voltage/current 

12 V 10 mA 

Conventional thermal current Ith 

max 5A 

Total current through terminal 15 

max 5A 

Switching capacity max AC cos φ = 1 

1500 VA 

Switching capacity max DC (ohmic) 

0.3 A 300 V; 0.4 A 120 V; 0.8 A 60 V; 5 A 30 V 

Electrical contact life cos φ = 1 

cos φ = 1 -> 5 x 105 switching cycles at 250 V / 2 A 

Durability of mechanical contact 

3 x 107 switching cycles 

Short circuit resistance (NO) 

Short circuit resistance (NC) 

4 A slow action or LS switch B4 3.15 A slow action  

Capacity Utilization category 

AC-15. 

Ie = 3 A 

Ue = 250 V 

Nominal operating current Nominal 
operating voltage 

DC-13 
DC-13 
DC-13. 

Ie = 2 A Ie 
= 0,4 A 
Ie = 0.2 A 

Ue = 24 V Ue = 
120 V 
Ue = 240 V 
 

Transducer connection 

 

Connectable transducers 

1 STWA1(H) transducer or potential free contact, or 1 S1 

current sensor per channel. 

AC internal resistance 

ca. 15kΩ 

Overload capacity STWA1(H) 

max 100A continuous, max 300A for 10s 

 

Voltage U 

 

 

 

Parameters 

17 … 21V; 
max 120mA at 230V Us (max 8x current sensor S1) max 10mA 

at 24V Us (max 0x current sensor S1) 

 

Testing conditions 

EN 61010-1 

Rated withstand surge voltage 

4000V 

Overvoltage category 

III 

Degree of contamination 

Rated insulation voltage Ui 

300V 

Work cycle 

100% 

 

EMC tests 

EN 61326-1 industrial environment 

Interference emission 

EN 61326-1; CISPR 11 Class B 

Interference immunity 

EN 61326-1 industrial environment 

Rapid transient disturbances/impacts 

EN 61000-4-4 ±4.5 kV 

 

pulses 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms 

High energy surge voltage (SURGE) 

IEC 61000-4-5 ±2 kV 

 

Environmental conditions 

 

Permissible ambient temperature 

-20 °C ... +65°C 

Permissible storage temperature 

-20 °C …+70 °C 

Содержание STW81V

Страница 1: ...Grid and Plant Protection Operating Manual STW81V updated 2022 09 21 Um For more information and help about this product please scan the QR Code or choose the following link STW81V Operating manual Quick guide Datasheet Connection diagram CAD Data Firmwareupdates FAQ Videos about installation and settings Certificates STW81V 12380 0710 00 Page 1 8 www ziehl de Current relay 8 channel single evalua...

Страница 2: ... with the following instructions is mandatory to ensure the functionality and safety of the product If the following instructions given especially but not limited for general safety transport storage mounting operating conditions commissioning and disposal recycling are not observed the product may not operate safely and may cause a hazard to the life and limb of users and third parties Deviations...

Страница 3: ...nputs Usage The STW81V current relay is particularly suitable for the central control of gate valves in extraction systems to be actuated according to the operating status of individual machines It can simultaneously control the central extraction system 5 Functional overview OR 8 inputs I1 I8 individual evaluation of 8 machines STWA1 H current sensor S1 or contact 8 relays for sliders with open a...

Страница 4: ...responding relay activates and the yellow LED goes on If the current on STWA1 H falls below the set switching threshold the corresponding relay is de energized with a fixed delay of 10 seconds If it is the last relay energized it switches off 20 s after K9 At the same time all 8 inputs are OR connected If current is detected in at least one of the monitored circuits relay K9 closes contacts 95 98 ...

Страница 5: ...gulations for the installation and operation of electrical systems The devices are built and tested according to DIN VDE EN IEC standards and leave the factory in perfect safety condition To maintain this condition follow the safety instructions in the manual marked Caution Failure to follow the safety instructions could result in death personal injury or property damage to the device itself and t...

Страница 6: ...corresponding input of STW81V in parallel to the current transducer STWA1 H 750 Ω resistor increase by a factor 2 330 Ω resistor increase by a factor 4 Due to large tolerances that must be considered we recommend that the best values be determined by trial and error method Length of connecting cables STWA1 H Up to 50 m but much longer are also possible Shielding may be required when laid parallel ...

Страница 7: ...action Capacity Utilization category AC 15 Ie 3 A Ue 250 V Nominal operating current Nominal operating voltage DC 13 DC 13 DC 13 Ie 2 A Ie 0 4 A Ie 0 2 A Ue 24 V Ue 120 V Ue 240 V Transducer connection Connectable transducers 1 STWA1 H transducer or potential free contact or 1 S1 current sensor per channel AC internal resistance ca 15kΩ Overload capacity STWA1 H max 100A continuous max 300A for 10...

Страница 8: ...torque 8 mm 0 5 Nm Degree of protection Casing terminals IP 30 IP20 Fastening Snap on mounting on 35 mm mounting rail according to EN 60 715 or screw fixing M 4 additional clamp is not included Weight approx 300 kg Subject to technical changes 2 Type V8 Dimensions in mm 1 Upper part cover 2 Bottom part base 3 Snap bar for snap mounting 4 Sealing latch 5 Front panel insert front panel 6 Position do...

Отзывы: