6.8 Factory setting
Default settings:
Input: [10 V] -> DC 0
– 10 V
Output: 0
– 10V, 0 – 20 mA
6.9 Query of firmware-version
from firmware 0-04:
•
Keep [Set] button pressed (
≥ 5s)
LEDs indicate the firmware version by fast blinking
(binary coded, LED 300V = bit0 … LED ON = bit3)
LED
300 V
10 V
mV
ON
Bit No. (value)
0 (1)
1 (2)
2 (4)
3 (8)
example (LED)
off
off
flash
off
➔
Version 0-04
6.9.1 Revision Firmware
Version 0-04:
•
additional predefined standard ranges (-
10…10V, -60…60mV, -150…150mV, -300…300mV)
7
Maintenance and repair
ZIEHL industrie-elektronik GmbH + Co KG
Daimlerstr.13
D-74523 Schwaebisch Hall
Phone: +49 791 504-0
Fax: +49 791 504-56
E-Mail: [email protected]
Homepage:
8
Error search
Wrong output signal (current/voltage) OUT (terminal 1
– 2 – 3)
Cause
The device is not configured correctly
Remedy
Check commissioning
For selected output range 4-20 mA (2-10V) the current is < 3,8 mA ( the voltage is <1,9V)
Cause
Sensor short-circuit or sensor interruption
Remedy
Check sensor/wire at terminal 5-6-7