Check PTCs only with measuring voltages of < 2.5 V.
5.6 Safe Separation
PTC-thermistor circuit (T1, T2) has a safe separation to low-voltage electric circuits PELV (T37, Logic Out and Interface). -> Technical data.
5.7 Stop Function, Stop Category 0
A stop function released by the protection device must transfer the machine after manipulation of this function as fast as possible into a safe condition.
The stop function must have top priority.
In case of failure the MS 220 DA motor protection causes a stop command at the Safe Stop T37 and the drive directly stop the engine.
5.8 Start and Restart
A restart may take place automatically only if no dangerous condition can be present.
The MS 220 DA motor protection switches on automatically when the engine has cooled down. If automatically restart is programmed additional measures
are required to prevent a restart of the engine in case of risk of a dangerous situation.
5.9 Manual Resetting
After introducing a stop by the protection device this must be maintained, until the manual resetting mechanism is operated and safe conditions for a
restart are given. The manual resetting may only be possible, if all safety functions and protection devices are effective.
5.10 Additional Notes for the SIL Category According EN 61508
The safety function must be tested within regular intervals. It is recommended to test once annually or within the maintenance cycle of the plant. For
recurring examinations of electrical systems in hazardous areas the inspection period must be kept within 3 years. One fault is recognized by the safety
test. One fault between safety tests can cause the loss of protection.
The following must be tested additionally to recurring examinations with maintenance services:
Short circuit test: resistance 20
Ω
in parallel to sensor terminals T1, T2
Line interruption test: disconnect sensor line at terminal T1 or T2
Temperature test: increase resistance 50…1500
Ω
to 4000
Ω
The tripping function will be stated at the drive display and can be manually reset when the failure is removed. If an error is detected no restart must be
induced until the error is cleared.
5.11 Maintenance and Repair
The device is maintenance-free. Only the manufacturer may accomplish repairs. EN 60079-17 and/or EN 50281-1-2 are to be observed.
5 Safety Instructions and References
Motor Protection MS 220 DA
12
MG33V102 - VLT
®
is a regisered Danfoss trademark
5
Содержание MS 220 DA
Страница 3: ......
Страница 9: ...3 Assembly Motor Protection MS 220 DA 6 MG33V102 VLT is a regisered Danfoss trademark 3 ...
Страница 11: ...4 Technical Data Motor Protection MS 220 DA 8 MG33V102 VLT is a regisered Danfoss trademark 4 ...
Страница 18: ...7 Certificates Motor Protection MS 220 DA 7 Certificates MG33V102 VLT is a regisered Danfoss trademark 15 7 ...
Страница 19: ...7 Certificates Motor Protection MS 220 DA 16 MG33V102 VLT is a regisered Danfoss trademark 7 ...
Страница 20: ...Motor Protection MS 220 DA 7 Certificates MG33V102 VLT is a regisered Danfoss trademark 17 7 ...
Страница 21: ...7 Certificates Motor Protection MS 220 DA 18 MG33V102 VLT is a regisered Danfoss trademark 7 ...
Страница 22: ......
Страница 24: ...forintegrationwiththe VLT AutomationDrive FC 302 Operating Instructions MCB 112 PTCThermistor Card ...
Страница 25: ......
Страница 37: ...4 How to Install MCB 112 VLT PTC Thermistor Option 12 MG 33 V2 02 VLT is a registered Danfoss trademark 4 ...
Страница 41: ...5 Parameter Setup MCB 112 VLT PTC Thermistor Option 16 MG 33 V2 02 VLT is a registered Danfoss trademark 5 ...