8.7 Display mode
(last decimal point off)
In the display mode, the COSFI100V is in the normal state; the current cos
and/or active current is
displayed here depending on the program. In addition, the alarm messages (e.g.
8
A1
88
,
8
a2L
8
,…) and
error codes (e.g.
8
Er1
8
,
8
Er2
8
, …) are also displayed.
Function key
Set / Reset
Press briefly: Changes the limits in PR 1 and 2
(only if Easy Limit is enabled)
Press for > 2 s: Resets after locked alarm
Press for > 4 s: Display program
Press for > 10 s: Displays the software version e.g.
8
00.0
8
Function key
Up / Down
Press briefly: Changes into the menus mode
Press for ≥2 s: Displays MAX and MIN measurements,
additionally pressing the Set key for
≥ 2s deletes the saved values
8.8 Menu mode
(last decimal point on)
The menu mode is used to select the menu items. If no key is pressed for 30s, one automatically
returns to the display mode.
Function key
Set / Reset
Press briefly: Changes into the configuration mode
Press for ≥2 s: Returns to the display mode (the most recently set
values are then applied)
Function key
Up / Down
Press briefly: Selects menu item; switches to the
display mode
8.9 Configuration mode
(last decimal point flashes)
The value of a parameter can be set in the configuration mode. The display continually alternates between
the parameter name and the currently set value until the Up/Down key is pressed, which changes the
value of the parameter. If no key is pressed for 2s, the display starts alternating again.
If no key is pressed for 30s (simulation mode 15 min), one automatically returns to the display mode (the
most recently set value is applied during this)
Function key
Set / Reset
Press briefly: The settings are applied; continues to
next parameter. After the last
parameter, change into menu mode
Press for
≥2 s: Returns to the display mode (the most recently set
values are then applied)
Function key
Up / Down
Press short/long: Changes the parameter value
(fast/slow)
Hint: Pressing the Up and Down keys simultaneously sets the adjustable value to zero. If you keep the Up or
Down key pressed while setting a value, the speed of the change in the display is accelerated.