4.4 Motor connection
The motor leads are connected to the terminals: PE, U1, U2. Several fans can be
connected to the controller - the maximum total current of all motors must not exceed the
current rating for the controller.
Information
Motor thermostats cannot be connected to these controller. I.e. a separate motor
protection is required. We cannot under any circumstances accept liability for damage to
the motors which do not have the required motor protection. It is recommended that
every fan is equipped with a separate motor protection unit e.g. type S-ET10!
5 Enclosure
5.1 Technical data
Line voltage: 1 ~ 230 V (-15 % / +10 %), 50/60 Hz
Max. ambient temperature: 40
°
C
Output voltages: 65 V - 110 V - 135 V - 170 V - 230 V
Type
Part-No.
Rated current
[A]
Max. line fuse
[A]
Max. heat dissi-
pation approx.
[W]
Weight
[kg]
Housing protec-
tion
RAE-2G
302067
2.0
T 4
20
3.3
IP54
RAE-4G
302068
4.0
T 6
30
4.55
IP54
RAE-7G
302069
7.0
T8
40
6.05
IP54
RAE-9G
302061
9.0
T16
50
10.5
IP54
Operating Instructions
RAE-2/4/7/9G
Enclosure
L-BAL-E283-GB 1928 Index 002
Part.-No.