3.5 Disposal / recycling

Disposal must be carried out professionally and in an environmentally friendly way in 
accordance with the respective national legal stipulations.

"

Separate the materials by type and in an environmentally friendly way.

"

If necessary, commission a specialist company with the waste disposal.

4 Installation

4.1 General notes

Attention!

Mounting, electrical connection, and start-up operation may only be carried out by an 
electrical specialist in accordance with electrotechnical regulations (e.g. EN 50110, 
EN 60204, IEC 364)!

The 5 electrical safety rules must be observed!

Cover neighbouring electrical equipment during installation work.

Before installation remove the device from the packing and check for any possible 
shipping damage! Start-up is not allowed in the case of transport damage!

At a weight greater than 25 kg for men / 10 kg for women, the device should be lifted 
out by two persons (according to REFA). The values may differ from country to 
country.

Wear safety shoes and gloves for handling!

Assemble the device on a clean and stable base. Do not distort during assembly! Use 
the appropriate mounting devices for proper installation of the unit!

Do not mount equipment on vibrating base!

Do not allow drilling chips, screws and other foreign bodies to reach the device 
interior!

The device should be installed in a location where it will not be disturbed, but at the 
same time can be easily accessed!

Depending on the housing model use supplied stoppers for cable inlets, cut off 
necessary cable inlets respectively to the cable diameter. Or alternative use cable 
inlet for cable glands. Any cable ducts openings not used must be sealed!

The required protective earth connection is established using screws between the 
housing parts in metal terminal space covers and housing casings. Commissioning is 
only permissible after these screws have been properly attached!

Metal screwed-connections are not permitted in plastic housing parts because there 
is no potential equalization.

Care must be taken to avoid direct radiation from the sun!

The device is designed for vertical installation (cable inlet down). A horizontal or 
reclined installation is only permissible after technical release of the manufacturer!

Be sure to observe proper heat dissipation (see Technical data, heat dissipation). 

Operating Instructions 

R-E-1.5...14G, RUE-2...7.5G

Installation

L-BAL-E191-GB 1735 Index 003

Part.-No. 

6/12

Содержание R-E-1.5G

Страница 1: ... 5 14G RUE 2 7 5G Transformer based controllers for variable voltage 1 motors Operating Instructions Keep for reference L BAL E191 GB 1735 Index 003 Part No english D GB DK E F I PL RU S www ziehl abegg com ...

Страница 2: ... 5 3 1 Function 5 3 2 Maintenance 5 3 3 Transport 5 3 4 Storage 5 3 5 Disposal recycling 6 4 Installation 6 4 1 General notes 6 4 2 Minimum space requirement 7 4 3 Mains connection 7 4 4 Motor connection 7 5 Enclosure 8 5 1 Technical data 8 5 2 Connection diagram 9 5 3 Dimensions mm 11 5 4 Manufacturer reference 12 5 5 Service information 12 Operating Instructions R E 1 5 14G RUE 2 7 5G L BAL E191...

Страница 3: ...y with these conditions will invalidate the guarantee on our controllers and accessories The 5 electrical safety rules must be observed It is strictly forbidden for work to be carried out on any components while they are connected to live voltage The open equipment is protected to IP00 It is possible to come into direct contact with dangerous voltages The safe isolation from the supply must be che...

Страница 4: ...anations of symbols Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows Attention General hazardous area Death or severe injury or significant property damage can occur if the corresponding precautions are not taken Danger due to electric current Danger by dangerous electric voltage Death or severe injury can occur if the correspo...

Страница 5: ...ional voltage output 230 V terminal L 1 is activated if fan runs at steps 1 2 3 4 or 5 It could be used e g for a signal lamp or damper control maximum load see connection diagram Attention Automatically restart after a power failure or mains disconnection 3 2 Maintenance The device must be checked for soiling and if necessary cleaned in periodic intervals 3 3 Transport The device is packed ex fac...

Страница 6: ...e appropriate mounting devices for proper installation of the unit Do not mount equipment on vibrating base Do not allow drilling chips screws and other foreign bodies to reach the device interior The device should be installed in a location where it will not be disturbed but at the same time can be easily accessed Depending on the housing model use supplied stoppers for cable inlets cut off neces...

Страница 7: ... technical data and rating plate affixed to the side The mains voltage must comply with the EN 50160 quality characteristics and the defined standard voltages in IEC 60038 Danger due to electric current The integrated autotransformer is not short circuit proof it is essential to note the size of the internal fuse and the maximum prefuse see technical data 4 4 Motor connection The motor leads are con...

Страница 8: ...ion R E 1 5G 302001 1 5 T 4 20 1 74 IP54 R E 2G 302107 2 0 16 T 4 20 2 1 IP54 R E 3 5G 302108 3 5 16 T 4 30 3 5 IP54 R E 6G 302109 6 0 16 T 8 35 4 9 IP54 R E 7 5G 302053 7 5 T 8 40 6 0 IP54 R E 9G 302055 9 0 T 16 50 10 5 IP54 R E 12 302056 12 0 T 20 80 9 1 IP21 R E 14G 302057 14 0 T 20 105 12 5 IP54 RUE 2G 302063 2 0 T 4 25 3 55 IP54 RUE 4G 302064 4 0 T 6 35 4 8 IP54 RUE 7 5G 302065 7 5 T 8 45 6 3...

Страница 9: ... AC 230 V 1 A N L 3 1 RENT05K2 06 09 2016 R E 2 3 5 6G N L1 PE L1 N U1 U2 N L M 1 U1 U2 PE Kontaktbelastung Contact rating max AC 230 V 1 A Netz Line 1 230 V 50 60 Hz 1 Motor ohne Thermostatschalter without thermostats 1 2 3 L PE PE 1 Line 1 230 V 50 60 Hz 2 1 motor without thermostats 3 Contact rating 230 V AC max 1 A Operating Instructions R E 1 5 14G RUE 2 7 5G Enclosure L BAL E191 GB 1735 Inde...

Страница 10: ...thermostats 2 U1 U2 1 2 Kontaktbelastung Contact rating max AC 230 V 1 A N L 3 1 4 3 4 5 6 7 A B Schaltuhr Time switch AC 230 V 1 Line 1 230 V 50 60 Hz 2 1 motor without thermostats 3 Contact rating 230 V AC max 1 A 4 Time switch Operating Instructions R E 1 5 14G RUE 2 7 5G Enclosure L BAL E191 GB 1735 Index 003 Part No 10 12 ...

Страница 11: ...5 3 Dimensions mm R E 1 5G R E 2 3 5 6G RUE 2 4 7 5G R E 7 5G R E 9 12 14G Operating Instructions R E 1 5 14G RUE 2 7 5G Enclosure L BAL E191 GB 1735 Index 003 Part No 11 12 ...

Страница 12: ... our technical support for control systems ventilation technology phone 49 0 7940 16 800 Email fan controls service ziehl abegg de Our worldwide contacts are available in our subsidiaries for deliveries outside of Ger many see www ziehl abegg com If you make returns for inspections or repairs we need certain information in order to facilitate focused trouble shooting and fast repair Please use our...

Отзывы: