LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PT PRIMARY
INVALID VALUE
Valid range of PT primary setting value is from
If value outside the range is entered, It will display “INVALID VALUE”
followed by correct range of parameter.
100 VL-L to 692.8 KVL-L.
3.2.1.2 Potential Transformer secondary Value
The value must be set to the nominal full scale secondary voltage which will be obtained from the
the Transformer when the potential transformer(PT)primary is supplied with the voltage defined
in 3.2.1.1 potential transformer primary voltage. The ratio of full scale primary to full scale
secondary is defined as the transformer ratio.
Here again 0 to 9 digit input keypad is provided to set value of PT
Secondary, & user can confirm this value with a simple touch on
This screen can be accessed only from system parameters list menu.
“ key”.
ENTER
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PT SECONDARY
ENTER PT SECONDARY VALUE(L-N)
16
1
2
3
4
5
6
7
8
9
DEL
ENTER
0
K
BACK
.
1
2
3
4
5
6
7
8
9
DEL
ENTER
0
K
BACK
.
Potential Transformer secondary ranges for various Input Voltages
63.5V L-N
57.73V - 69.28V L-N
69.86V - 138.56V L-N
139.14V - 277.12V L-N
133.0V L-N
239.6V L-N
Valid range of PT
value is from
secondary setting
241.0 to 480.0.
If value outside the range is entered, It will display “INVALID VALUE”
followed by correct range of parameter.
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
LINE-NEUTRAL VOLTAGE
PT SECONDARY
INVALID VALUE
for 415 VL-L. Please refer the table bellow for different ranges.