3. Parameters
The first parameter to show up during Set-up mode is the Set Point. Other
parameters, their default, minimum and maximum values are shown in the
below table:
Parameter
Default Displayed
Min.
Max.
Value
Code
Set Point (°C)
5
0
30
Min. Expected Ambient
1
(°C)
–20
–30
0
Pipe Size
2
1
1
3
Heater Operation if
1
0 (OFF) 1 (ON)
Sensor Error
Voltage Free Operation
0
0 (NO) 1 (YES)
1
Min. Expected Ambient Temp. is the temperature whereby the heating
cable is energized for 100%.
Min. Expected Ambient Temp. can only be set in steps of 10 K.
Min. Expected Ambient = Low Temp. Alarm.
2
Select Pipe Size Diameter:
3 for pipes
≥
2 inch.
2 for pipes
≥
1 inch.
1 for pipes
<
1 inch.