The following screens allow the user to reset the Demand and Maximum Demand readings.

Note: Resetting the Demand will automatically reset the Maximum Demands (MaxAD and MaxkVAD).

Reset (None)

Pressing “

Up” key returns the product to

measurement reading screens.

Pressing the “

Down” key will enter the “Reset

Parameter Select” mode and scroll the “value”
through the parameters None and d wrapping back
to None.

Pressing the “

Up” key will not reset demand and

return to measurement reading screens.

Reset parameters select, (Reset Demands)

The user has scrolled through to the “d” (Demands)
value.

Pressing the “

Up” key will select the value and

advance to the “Reset Demands Confirmation” Mode.

Reset Demands Confirmation.

Pressing the “

Down” key will re-enter the “Reset

Parameter Select mode.

Pressing the “

Up” key resets the Demand

readings and returns the product to measurement
reading screens.

SysV

SysA

Hz

SysV

SysA

Hz

SysV

SysA

Hz

4. Ins tall ation

Mountin g is by fou r side clam ps, slid e the sid e clamp s throug h side

slot ti ll side clam p gets firm ly locke d in a groov e (Refer fig .) Considera tion
shoul d be give n to th e space require d behin d th e ins trumen t to allo w fo r bends
in the connectio n cables.

As the front of the enclosure conforms to IP54 it is protected from water spray
from all directions, additional protection to the panel may be obtained by the
use of an optional panel gasket. The terminals at the rear of the product
should be protected from liquids.

The instrument should be mounted in a reasonably stable ambient
temperature and where the operating temperature is within the range

0

-10 to 55 C. Vibration should be kept to a minimum and the product should
not be mounted where it will be subjected to excessive direct sunlight.

SLIDE IN THIS DIRECTION AND LOCK

PANEL

Front

2.

Vol tage s dang erous to hu man lif e are pres ent at some of the term inal
co nnectio ns of this unit . En sure that all su pplie s are de -energise d be fore
att emptin g any conne cti on or disco nnecti on.

3.

Thes e prod ucts do not ha ve interna l fus es th erefor e externa l fuses must
be used to ens ure safe ty und er faul t condi tio ns.

4.1 EMC Installa tion

This product has been designed to meet the certification of the EU directives
when installed to a good code of practice for EMC in industrial environments,
e.g.

1.

Screened output and low signal input leads or have provision for fitting
RF suppression components, such as ferrite absorbers, line filters etc., in
the event that RF fields cause problems.

Note:I t is good practice to install sensitive electronic instruments that are
performing critical functions, in EMC enclosures that protect against electrical
interference which could cause a disturbance in function.

2.

Avoid routing leads alongside cables and products that are, or could be,a
source of interference.

3.

To protect the product against permanent damage, surge transients must
be limited to 2kV pk. It is good EMC practice to suppress differential
surges to 2kV at the source. The unit has been designed to automatically
recover in the event of a high level of transients. In extreme
circumstances it may be necessary to temporarily disconnect the
auxiliary supply fora period of greater than5 seconds to restore correct
operation.

4.

ESD precautions must be taken at all times when handling this product.

4.2 Case Dime nsion

The Current inputs of these products are designed for connection in to
systems via Current Transformers only, where one side is grounded.

4.4 Auxilia ry Sup ply

Meter should ideally be powered from a dedicated supply, however
it may be powered from the signal source, provided the source remains within
the limits of the chosen auxiliary voltage.

3.78”

96mm

FRONT DISPLAY

AREA

3.78”

96mm

4.3 Wiring

Input connections are made directly to screw-type terminals with indirect
wire pressure. Numbering is clearly marked in the plastic moulding. Choice of
cable should meet local regulations. Terminal for both Current and Voltage
inputs will accept upto 3mm x 2 diameter cables.

2

x10 00

Sys kVA

x10 00

AD

kVAD

x10 00

Ma x AD

Max kVAD

x10 00

Sys kVA

x1000

AD

kVAD

x10 00

Ma x AD

Max kVAD

x10 00

Sys kVA

x1000

AD

kVAD

x10 00

Max AD

Max kVAD

Not e: It is reco mmende d to us e wir e wit h lu g for

connectio n wit h mete r.

Requirements

and Panel Cut Out

3.15”

80mm

MAX PANEL THICKNESS 0.18”,5mm

PANEL CUTOUT

3.62”

92mm

3.62”

92mm

a qualifi ed engi neer, abi din g by an y local regula tio ns.

In th e intere st of sa fety and fu nct ional ity this pro duc t must be installe d by

1.

Caution

3.2.5. Deman d Reset

www.ziegler-instruments.com

4

|

6

Содержание 3410

Страница 1: ...rocedures for configuring the instrument for individual user requirements To access the set up screens press and hold the Key simultaneously for5 seconds This will take the User into the Password Protection Entry Stage Section 3 1 3 1 Passwor d Protection Screen 3 Apparent Power kVA demand and Max kVA demand Password protection can be enabled to prevent unauthorised access to set up Down and Up Sy...

Страница 2: ...Up key advances the operation to the Up digit and sets the second digit in this case to 1 SysV SysA Hz x1000 Neutr alA Sys kVA x1000 AD kVAD x1000 Max AD Max kVAD SysV SysA Hz x1000 Sys kVA x1000 AD kVAD x1000 Max AD Max kVAD New Change Password second digit entered prompting for third digit decimal point indicates that this will be flashing Pressing the Down key will scroll the value of the third...

Страница 3: ... Up less significant digit Value See section 3 2 2 position At this stage the decimal point will flash Potential Transformer Primary Value Confirmation stage flashing at the hundreds of volts position 3 2 2 Curren t Primary Value Transformer Secondary Value See section 3 2 3 will be restricted selected flashing nominal voltage i e 250 MVA nominal system power Current Transformer Primary Value Conf...

Страница 4: ...signed to meet the certification of the EU directives when installed to a good code of practice for EMC in industrial environments e g 1 Screened output and low signal input leads or have provision for fitting RF suppression components such as ferrite absorbers line filters etc in the event that RF fields cause problems Note I t is good practice to install sensitive electronic instruments that are...

Страница 5: ...0 of Rated Value 0 5 of range 10 100 of Rated Value 0 For range of use 0 50 C Rated Value Error change due to variation of an influence quantity 2 Error allowed for the reference condition applied in the test Referenc e condition s for Accuracy 0 23 C 2C 50 or 60 Hz 2 Sinusoidal distortion factor 0 005 Rated Value 1 Reference temperature Input frequency Input waveform Auxiliary supply voltage Auxi...

Страница 6: ...re front only Enclosure 96mm x 96mm DIN Quadratic Polycarbonate Housing 80 mm 0 620 kg Approx Style Material Terminals Depth Weight Screw type terminals Self extinguish non dripping as per UL 94 V 0 www ziegler instruments com 6 6 ZIEGLER INSTRUMENTS Schnepfenreuther Weg 6 D 90425 Nürnberg Germany 49 911 38 492 45 TEL 49 911 32 26 212 FAX info ziegler instruments com www ziegler instruments com E ...