The following screens allow the user to reset the Demand and Maximum Demand readings.
Note: Resetting the Demand will automatically reset the Maximum Demands (MaxAD and MaxkVAD).
Reset (None)
Pressing “
Up” key returns the product to
measurement reading screens.
Pressing the “
Down” key will enter the “Reset
Parameter Select” mode and scroll the “value”
through the parameters None and d wrapping back
to None.
Pressing the “
Up” key will not reset demand and
return to measurement reading screens.
Reset parameters select, (Reset Demands)
The user has scrolled through to the “d” (Demands)
value.
Pressing the “
Up” key will select the value and
advance to the “Reset Demands Confirmation” Mode.
Reset Demands Confirmation.
Pressing the “
Down” key will re-enter the “Reset
Parameter Select mode.
Pressing the “
Up” key resets the Demand
readings and returns the product to measurement
reading screens.
SysV
SysA
Hz
SysV
SysA
Hz
SysV
SysA
Hz
4. Ins tall ation
Mountin g is by fou r side clam ps, slid e the sid e clamp s throug h side
slot ti ll side clam p gets firm ly locke d in a groov e (Refer fig .) Considera tion
shoul d be give n to th e space require d behin d th e ins trumen t to allo w fo r bends
in the connectio n cables.
As the front of the enclosure conforms to IP54 it is protected from water spray
from all directions, additional protection to the panel may be obtained by the
use of an optional panel gasket. The terminals at the rear of the product
should be protected from liquids.
The instrument should be mounted in a reasonably stable ambient
temperature and where the operating temperature is within the range
0
-10 to 55 C. Vibration should be kept to a minimum and the product should
not be mounted where it will be subjected to excessive direct sunlight.
SLIDE IN THIS DIRECTION AND LOCK
PANEL
Front
2.
Vol tage s dang erous to hu man lif e are pres ent at some of the term inal
co nnectio ns of this unit . En sure that all su pplie s are de -energise d be fore
att emptin g any conne cti on or disco nnecti on.
3.
Thes e prod ucts do not ha ve interna l fus es th erefor e externa l fuses must
be used to ens ure safe ty und er faul t condi tio ns.
4.1 EMC Installa tion
This product has been designed to meet the certification of the EU directives
when installed to a good code of practice for EMC in industrial environments,
e.g.
1.
Screened output and low signal input leads or have provision for fitting
RF suppression components, such as ferrite absorbers, line filters etc., in
the event that RF fields cause problems.
Note:I t is good practice to install sensitive electronic instruments that are
performing critical functions, in EMC enclosures that protect against electrical
interference which could cause a disturbance in function.
2.
Avoid routing leads alongside cables and products that are, or could be,a
source of interference.
3.
To protect the product against permanent damage, surge transients must
be limited to 2kV pk. It is good EMC practice to suppress differential
surges to 2kV at the source. The unit has been designed to automatically
recover in the event of a high level of transients. In extreme
circumstances it may be necessary to temporarily disconnect the
auxiliary supply fora period of greater than5 seconds to restore correct
operation.
4.
ESD precautions must be taken at all times when handling this product.
4.2 Case Dime nsion
The Current inputs of these products are designed for connection in to
systems via Current Transformers only, where one side is grounded.
4.4 Auxilia ry Sup ply
Meter should ideally be powered from a dedicated supply, however
it may be powered from the signal source, provided the source remains within
the limits of the chosen auxiliary voltage.
3.78”
96mm
FRONT DISPLAY
AREA
3.78”
96mm
4.3 Wiring
Input connections are made directly to screw-type terminals with indirect
wire pressure. Numbering is clearly marked in the plastic moulding. Choice of
cable should meet local regulations. Terminal for both Current and Voltage
inputs will accept upto 3mm x 2 diameter cables.
2
x10 00
Sys kVA
x10 00
AD
kVAD
x10 00
Ma x AD
Max kVAD
x10 00
Sys kVA
x1000
AD
kVAD
x10 00
Ma x AD
Max kVAD
x10 00
Sys kVA
x1000
AD
kVAD
x10 00
Max AD
Max kVAD
Not e: It is reco mmende d to us e wir e wit h lu g for
connectio n wit h mete r.
Requirements
and Panel Cut Out
3.15”
80mm
MAX PANEL THICKNESS 0.18”,5mm
PANEL CUTOUT
3.62”
92mm
3.62”
92mm
a qualifi ed engi neer, abi din g by an y local regula tio ns.
In th e intere st of sa fety and fu nct ional ity this pro duc t must be installe d by
1.
Caution
3.2.5. Deman d Reset
www.ziegler-instruments.com
4
|
6